3

Installation

WARNING
High pressure! Injury to skin and eyes possible! Be careful when
opening connections on a pressurized item.
3.1

Compressor handling

3.1.1 Delivery

Please check whether the delivery is correct and complete. Any deficiency should be reported
immediately in writing.
Standard delivery:
 Suction and discharge shut-off valves
 Oil charge, oil sight glass
 Mounting kit
 CoreSense™ Diagnostics or CoreSense™ Protection module
 Holding charge up to 2.5 bar(g) (dry air)

3.1.2 Transport and storage

WARNING
Risk of collapse! Personal injuries! Move compressors only with
appropriate mechanical or handling equipment according to weight. Keep in
the upright position. Do not stack pallets on top of each other. Keep the
packaging dry at all times.
Figure 4
Compressors are delivered on pallets. Cooling fans are delivered in separate boxes.
Accessories may be mounted or delivered loose. Solenoid valves are never mounted.

3.1.3 Positioning and securing

IMPORTANT
Handling damage! Compressor malfunction! Only use the lifting eyes
whenever the compressor requires positioning. Using discharge or suction
connections for lifting may cause damage or leaks.
If possible, the compressor should be kept horizontal during handling.
For safety reasons two lifting eyes should be fitted before moving a compressor (½" - 13 UNC).
Otherwise refer to drawings on Figure 5 to see how to apply other lifting methods.
4M*
max. 220 kg
Figure 5
C6.3.1/0116-0716/E
6M*
max. 260 kg