Trane BAYAIR30AVENTA Installer's Manual
Trane BAYAIR30AVENTA Installer's Manual

Trane BAYAIR30AVENTA Installer's Manual

Concentric vent kit for condensing furnaces and boilers

Advertisement

Quick Links

INSTALLER'S GUIDE
ALL phases of this installation must comply with
NATIONAL, STATE AND LOCAL CODES.
BAYAIR30AVENTA
Model:
Concentric Vent Kit for
Condensing Furnaces and Boilers
For use with *UH, *DH, M95, *UY, *DY, *UX, *DX,
*UC, *DC model Furnaces and TGCW130A90M0A
and TGXWW130A90M0A boilers
* may be A or T or C
IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information pack upon completion of work.
WARNING
L
!
INSTALLATION OR REPAIRS MADE BY UNQUALIFIED
PERSONS CAN RESULT IN HAZARDS TO YOU AND OTH-
ERS. INSTALLATION MUST CONFORM WITH LOCAL CODES
OR, IN THE ABSENCE OF LOCAL CODES, WITH CODES OF
THE COUNTRY HAVING JURISDICTION. THE INFORMATION
CONTAINED IN THESE INSTRUCTIONS IS INTENDED FOR
USE BY A QUALIFIED SERVICE TECHNICIAN FAMILIAR WITH
SAFETY PROCEDURES AND EQUIPPED WITH THE PROPER
TOOLS AND TEST INSTRUMENTS. FAILURE TO CAREFUL-
LLY READ AND FOLLOW ALL INSTRUCTIONS IN THESE
INSTRUCTIONS CAN RESULT IN FURNACE OR BOILER
MALFUNCTION, PROPERTY DAMAGE, PERSONAL INJURY
AND/ OR DEATH.
NOTE: Codes and local utility requirements governing the
installation of gas fired equipment, wiring, plumbing, and
flue connections must be adhered to. In the absence of local
codes, the installation must conform with the Nation Fuel
Gas Code ANSI Z223.1 "latest edition", or CAN/ CGA B149
Installation Codes. The latest code may be obtained from the
American Gas Association Laboratories 400 N. Capitol St.
NW, Washington D.C. 20001, 1-800-699-9277 or www.aga.
com
NOTE: Read the Installer's Guide before starting the instal-
lation. Refer to the Furnace or boiler Installer's Guide for
equivalent vent lengths. The BAYAIR30AVENTA is 5 equiva-
lent feet.
INTRODUCTION
This Installer's Guide covers installation of the concentric vent
kit on all gas fired direct vent condensing furnaces.
L
!
INSTALLING AND SERVICING HEATING EQUIPMENT CAN
BE HAZARDOUS DUE TO GAS AND ELECTRICAL COMPO-
NENTS. ONLY TRAINED PERSONNEL SHOULD INSTALL OR
SERVICE HEATING EQUIPMENT. FAILURE TO FOLLOW THIS
WARNING CAN RESULT IN PRODUCT DAMAGE, PERSONAL
INJURY AND/OR DEATH.
WYE - CONCENTRIC FITTING
1
CONCENTRIC VENT KIT
© 2012 Trane
All Rights reserved
WARNING
4" SDR-26 PIPE
2-1/2" SDR-26 PIPE
RAIN CAP
Library
Product Section
Product
Model
Literature Type
Sequence
Date
File No.
Supersedes
NOTE:
Canada requires that all Category IV heating appliances use
venting material that meets ULC S636. This kit does not meet
these requirements and cannot be used.
DO NOT APPLY TO A NON-CONDENSING FURNACE.
NOTE: If these instructions differ from those packaged with
the furnace or boiler, follow these instructions.
DESCRIPTION AND USAGE
Kit Contents:
1 — Rain cap
1 — 4" Diameter SDR-26 Pipe, 23.75" Long
1 — 2
/
" Diameter SDR-26 Pipe, 33.12"
1
2
1 — Wye concentric Fitting
Only one vent kit per each furnace or boiler is allowed.
Vent kit is for 2, 2-1/2 or 3 in. diameter pipe systems, (See
Figures 3, 4, 5, and 6 for the different applications.) Both
the combustion air and vent pipes must attach to the vent
kit. The vent kit must terminate outside of the structure and
should be installed vertically as shown in Figures 3 and 4, or
horizontal as shown in Figures 5 and 6.
NOTE: The roof vent location is preferred since it is less
susceptible to damage, has reduced chances to intake con-
taminants, and vent vapors are less visible.
WARNING
L
!
THIS VENT KIT IS ONLY TO BE USED FOR VENTING CAT-
EGORY IV FURNACES AND CONDENSING BOILERS. DO
NOT USE TO VENT CATEGORY I, II OR III VENT FURNACES
OR BOILERS. FAILURE TO FOLLOW THIS WARNING COULD
RESULT IN FIRE, PERSONAL INJURY OR DEATH.
WARNING
L
!
DISCONNECT POWER SUPPLY BEFORE BEGINNING IN-
STALLATION TO PREVENT PERSONAL INJURY OR DEATH
FROM ELECTRICAL SHOCK AND EQUIPMENT DAMAGE.
Field supplied pipe and fittings are required to complete the
installation.
The combustion air and vent pipe and fittings must conform to
American National Standards Institute (ANSI) and American
Society for Testing and Materials (ASTM) standards D1785
(schedule-40 PVC), D2665 (PVC-DWV), D2441 (SDR-21 and
SDR-26 PVC), D2661 (ABS-DWV), or F628 (schedule-40 ABS).
Pipe cement and primer must conform to ASTM standards D2564
(PVC) or D2235 (ABS). In Canada, construct all combustion air
and vent pipes for this unit of CSA or ULC certified schedule-40
PVC/ABS-DWV pipe and pipe cement.
18-CH34D1-7
Service Literature
Unitary
Unitary Accessories
Vents
Installer's Guide
0
02/12
18-CH34D1-7
18-CH34D1-56

Advertisement

loading

Summary of Contents for Trane BAYAIR30AVENTA

  • Page 1 NOTE: Read the Installer's Guide before starting the instal- lation. Refer to the Furnace or boiler Installer's Guide for THIS VENT KIT IS ONLY TO BE USED FOR VENTING CAT- equivalent vent lengths. The BAYAIR30AVENTA is 5 equiva- EGORY IV FURNACES AND CONDENSING BOILERS. DO lent feet.
  • Page 2 INSTALLER'S GUIDE 3" DIA PVC INTAKE/ REMOVE RIBS COMBUSTION AIR FROM CAP VENT 4.5" DIA COMBUSTION MAINTAIN 12 IN. MINIMUM CLEARANCE ABOVE HIGHEST 21.125" (typ) ANTICIPATED SNOW LEVEL. MAXIMUM OF 35.2" (typ.) 24 IN. ABOVE ROOF. 3" DIA PVC MAIN BODY PIPES MAY BE VENT/EXHAUST LENGTHENED TO 60"...
  • Page 3 INSTALLER'S GUIDE MAINTAIN 12 IN. VENT MINIMUM CLEARANCE REMOVE RIBS ABOVE HIGHEST ANTICIPATED SNOW FROM CAP LEVEL. MAXIMUM OF 24 IN. ABOVE ROOF COMBUSTION ROOF BOOT (FIELD SUPPLIED) SUPPORT (FIELD SUPPLIED) ELBOW (FIELD SUPPLIED) COMBUSTION VENT CONCENTRIC VENT ROOF INSTALLATION CONCENTRIC VENT SIDE WALL INSTALLATION -SIDE WALL VENT (SEE FIGURE 5)
  • Page 4 This appliance requires a special venting system. If installed in every dwelling, building or structure used in BAYAIR30AVENTA or BAYVENT200B are used, a copy of whole or in part for residential purposes, including those the installation instructions for the kit shall remain with the owned or operated by the Commonwealth and where the side appliance or equipment at the completion of installation.