How To Set By Keys; Settings For Power Measurement - Panasonic KW2M-A User Manual

Eco-power meter
Hide thumbs Also See for KW2M-A:
Table of Contents

Advertisement

4.4 How to Set by Keys

■Set before measuring.
Select setting item with <ITEM/>> and press <SET>, and the value will be blinking.
Set with <ITEM/>> and <SHIFT/∧>.
When you select [Yes] with the confirmation window and press <SET>, the setting values are settled.
Setting items with (※) can be set to each CH and each unit.

4.4.1 Settings for power measurement

Phase/Wire system
Select phase/wire system to measure.
- 1
M
CT setting
Select using CT type.
- 1
M
P r i
a r y
m
S e c o n d a r y
To use CT with secondary side current 5A: [5]
To use CT with secondary side current 1A: [1]
Voltage setting
Set the rated voltage to measure.
- 1
M
P r i
a r y
m
S e c o n d a r y
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
(※)
Press <ITEM/>>, <SHIFT/∧> to select.
P o
e r
w
S y s t e
m
[Set list]
1P2W, 1P3W, 3P3W, 3P4W (initial: 1P2W)
1 P 2
W
* When the system is not matched with the measure
system, it doesn't measure correctly.
(※)
Press <SET>, to select primary or secondary.
P o
e r
w
T
C
Press <ITEM/>>, <SHIFT/∧> to set.
5 A
5 A
[Set range]
Primary side
Secondary side: 5 (5A), 1 (1A) (initial: 5)
SHIFT
ITEM
Press <SET>, to select primary or secondary.
P o
e r
w
V T
Press <ITEM/>>, <SHIFT/∧> to set the voltage.
2 3 0 V
2 3 0 V
[Set range]
Primary side
Secondary side: 100 to 690 (initial:230)
*Set the rated voltage when it doesn't use VT.
SHIFT
ITEM
: 1 to 65535 (initial:5)
Increase
decrease
: 100 to 500000 (initial:230)
Increase
decrease

Advertisement

Table of Contents
loading

This manual is also suitable for:

Akw263100aAkw272100a

Table of Contents