Installing/mounting

The probe face is magnetic. Keep it away from magnetosensitive materials such as
computer discs and audio or video tapes.
All field wiring must have insulation suitable for at least 250 V and the maximum ambient
temperature of +60°C (+140 °F).
Note
• The Protective Earth Terminal indicated by (
• All wiring must be done by qualified personnel in accordance with all governing
regulations.
• The equipment must be protected by a 15 A fuse or circuit breaker in the building
installation.
• A circuit breaker or switch in the building installation, marked as a disconnect switch, shall
be in close proximity to the equipment and within easy reach of the operator.
• Relay contact terminals are for use with equipment which has no accessible live parts
and wiring which has insulation suitable for at least 250 V.
SITRANS WM100
Operating Instructions, 07/2017, A5E45103494-AA
WARNING
WARNING
) must be connected to reliable ground.
4
7