Item
Average
processing
settings
Digital
Scale conversion
processing
setting
Offset setting
Gain setting
Upper/Lower limit comparison
Holding max./min. values
Disconnection detection
External connection method
Weight (main unit)
Consumption current
(Note 1) The full scale (F.S.) on the accuracy of a voltage range from 1 to 5 V DC and that of a current range from 4
to 20 mA are 0 to 5 V DC and 0 to 20 mA, respectively.
(Note 2) The indication accuracy in the high-speed mode is ±0.3% (at 0 to 55 °C).
(Note 3) The indication accuracy rating of the thermocouple range varies by the input type of the thermocouple to be
used and measurement temperature.
(Note 4) If highly accurate temperature data is necessary, use the temperautre data in about 30 minutes after the unit
was powered on.
(Note 5) If a sudden temperature change occurs in the unit, the accuracy may not be stable temporarily. Install to
keep the unit out of the direct wind from devices such as a cooling fan in a control panel.
REFERENCE
Also refer to the section "Indication accuracy rating of thermocouple range"
on the next page.
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Specifications
Number of averaging times, Time average, Moving average
A desired value within the range of ±30,000 (Voltage/current range only)
A desired value within the range of ±3,000
±10%
Possible to make settings on a channel-by-channel basis.
Possible to make settings on a channel-by-channel basis.
Available (Voltage range of 1 to 5 V, current range of 4 to 20 mA and
thermocouple range only)
Connection terminal block connection
145 g
80 mA or less