relay coil energized and the relay starting contacts
open. When power is shut off to the motor, the volt-
age drops to zero, the coil is de-energized, and the
start contacts reset.
When changing a compressor relay, care should be
taken to install the replacement in the same position
as the original.
Relay Type
Current Relay
PTC Relay
Potential Relay
28
Chapter 3
Table 3-7: Facts About Starting Relays
Compressor
Motor Type
RSIR and CSIR
RSIR and PSC
CSR
Figure 3-19. Potential type relay.
Characteristics
Sense starting current to main (run) windings
Contacts normally open
Contacts close and then release in less than 1 second
as motor starts
Must be installed vertically since contacts open by
gravity
Sense starting current to start winding
Solid state device whose resistance increases with
heat from current as motor starts
Takes 3 to 10 minutes to cool down between operating
cycles
Sense voltage generated by start winding
Contacts normally closed
Contacts open in less than 1 second as motor starts