Planning the use
3.4 Mounting Positions and Type of Fixation
Testing climatic ambient conditions
In the following table, contains the tests that were checked on the HMI device in regards to
the climatic ambient conditions for operation.
Ambient condition
Operating temperature
Humidity, relative
IEC 61131-2:2007
Humidity, absolute
Air pressure
IEC 60068-2-13:1983
Hazardous material
concentration
IEC 60721-3-3:1994
3.4
Mounting Positions and Type of Fixation
Mounting position
The HMI device is designed for mounting in:
● Racks
● Cabinets
● Control boards
● Consoles
In the following, all of these mounting options are referred to by the general term "cabinet".
The HMI device is self-ventilated and approved for vertical and inclined mounting in
stationary cabinets.
32
Permitted range
See Mounting Positions and
Type of Fixation (Page 32)
< 95 %,
No condensation
1 to 25 g/m
3
1080 to 795 hPa
SO
< 0.5 vpm,
2
relative humidity < 60%,
no condensation
H
S < 0.1 vpm,
2
relative humidity < 60%,
no condensation
Comment
–
–
–
Corresponds to an
elevation of –1000 to 2000 m
Test: 10 cm
/m
3
3
Test: 1 cm
/m
; 10 days
3
3
Operating Instructions, 10/2010, A5E03284305-01
; 10 days
KP8, KP8F