Installer Level Control Parameters

P30 Switching Differential
in Heating Mode
P38
Functionality of
P40
X1 and X2
P39
Operating action of
P41
X1, X2 as digital inputs
P48 Minimum on time for
2-position control
output
P49 Minimum off time for
2-position control
output
P51 Floor Heating Limit
Temperature
P53 Maximum Fan Speed
P54 Maximum Fan Swing
P65 Protection heating
setpoint
20
0.5 to 6.0 K
0: --- No function
1: Ext / Return Temp (AI)
3: Window open detect (DI)
6: Fault input (DI)
7: Monitor input (Digital)
8: Monitor input (Temp)
NO: Normally Open / Open
NC: Normally Close / Close
1...20 minutes
1...20 minutes
OFF, 10...50 °C
1 to 7
0: no swing function
1 to 10 positions
OFF, 5 ... WcoolPro;
WCoolPro = 40 °C max
1K
P38 à
X1 = 0
P40 à
X2 = 0
P39: X1=NO
P41: X2=NO
1 min.
1 min.
OFF
8 °C