OPERATION
6
Screen
6.4.3 HART® network configuration
INFORMATION!
For more data, refer to Networks on page 54
The device uses HART® communication to send information to HART®-compatible equipment. It
can operate in either point-to-point or multi-drop mode. The device will communicate in multi-
drop mode if you change the polling address.
CAUTION!
Make sure that the address for this device is different from others in the multi-drop network.
INFORMATION!
Make sure that menu item C5.1.1 Current Loop Mode is set to "On".
How to change from point-to-point to multi-drop mode
• Enter Program mode.
• Push 2 × [ ], [> > > > ], 3 × [ ], 2 × [> > > > ], [ ] and 2 × [> > > > ] to go to menu item C5.1.2.1 Polling Address.
• Enter the password used at this time for the "Expert" access level. If it is the default password,
enter "0058". Push [^ ^ ^ ^ ] to confirm.
• Enter a value between 001 and 063 and push [^ ^ ^ ^ ] to confirm.
• Push [^ ^ ^ ^ ] again and again to go back to the Save Configuration?
• Push [ ] or [ ] to set the screen to "Yes" and push [^ ^ ^ ^ ].
i
The output is set to multi-drop mode. The current output is set to 4 mA. This value does not
change in multi-drop mode.
How to change from multi-drop to point-to-point mode
• Enter Program mode.
• Push 2 × [ ], [> > > > ], 3 × [ ], 2 × [> > > > ], [ ] and 2 × [> > > > ] to go to menu item C5.1.2.1 Polling Address.
• Enter the password used at this time for the "Expert" access level. If it is the default password,
enter "0058". Push [^ ^ ^ ^ ] to confirm.
• Enter the value 000 and push [^ ^ ^ ^ ] to confirm.
• Push [^ ^ ^ ^ ] again and again to go back to the Save Configuration?
104
Steps
[ ] or [ ] to change the parameter
("Disable" or "Enable").
[^ ^ ^ ^ ] to confirm.
4 × [^ ^ ^ ^ ] to confirm.
[ ] or [ ] for the selection of the
save option (Yes, No or Back).
[^ ^ ^ ^ ] to confirm.
www.honeywellprocess.com
Empty Spectrum Enable. If you set the
menu item to "Enable", the device will use
the empty spectrum recording data. If you
set the menu item to "Disable", the device
will not use the empty recording data at
this time.
Save Configuration?
Save Configuration? screen.
Save Configuration?
Save Configuration?
Set to "Yes" to save and use the settings
and data and go back to Normal mode. Set
to "No" to cancel the changes to the device
settings and go back to Normal mode. Set
to "Back" to stay in Program mode.
.
Save Configuration?
Save Configuration? screen.
Save Configuration?
Save Configuration? screen.
Save Configuration?
Save Configuration?