Analog Value Objects - Lennox Prodigy 2.0 Application Manual

M3 unit controller
Hide thumbs Also See for Prodigy 2.0:
Table of Contents

Advertisement

12.5. Analog Value Objects

Optional Properties Supported:
Optional Writable Properties:
Object
Object Name
ID
1
Baud Rate Setting
Heating Occupied Set
130
Point
Cooling Occupied Set
131
Point
Heating Unoccupied
132
Set Point
Cooling Unoccupied
133
Set Point
Supply Airflow Low
134
Speed Target
Supply Airflow High
135
Speed Target
Supply Airflow Medium
136
Low Speed Target
Supply Airflow Medium
137
High Speed Target
Supply Airflow Heat
138
Mode Target
Ventilation Airflow
139
Target
140
Smoke Airflow Target
141
Outdoor Airflow Target
None
Present_Value
Table 45. Analog Value Objects List
Min.
Max.
Units
Value
Value
None
9600
76800
°F
40
95
°F
40
95
°F
40
95
°F
40
95
CFM
CFM
CFM
Refer to the Section 18.4., Airflow Target Min-Max
Settings for the valid value ranges of these para­
CFM
meters for an A box.
CFM
CFM
CFM
150 cfm/
CFM
0 cfm/ton
ton
CFM = cubic feet minute
Page 62
Valid Values within
Range
9600, 19200, 38400,
76800
All
For occupied and un­occupied set
All
the heating set point must be lower than
the cooling set point by at least the
auto−changeover dead­ band value set
All
in M3 Unit Controller Parameter 152
All
1. These objects are applicable only if
Advance Airflow (Smart Airflow
stalled in the system.
2. Object IDs 136 and 137 are not ap­
plicable to an A box.
3. Multiply the tonnage of the RTU with
the value in CFM/ton to derive the value
in CFM units.
All
Note
38400 default
points considered separately,
(default 3ºF).
®
) is in­