Parameters/Address Space; Measurement Types And Measuring Ranges - Siemens SIMATIC ET 200AL Manual

Simatic analog input module ai 4xu/i/rtd 4xm12 (6es7144-5kd00-0ba0)
Hide thumbs Also See for SIMATIC ET 200AL:
Table of Contents

Advertisement

Parameters/address space

4.1

Measurement types and measuring ranges

The table below indicates which measuring range is configurable.
Table 4- 1
Measurement type
Deactivated
Voltage
Current (4-wire transducer)
Current (2-wire transducer)
Resistance
(3-wire connection)
Resistance
(2-wire connection)
Resistance thermometer
(3-wire connection)
Resistance thermometer
(2-wire connection)
Analog input module AI 4xU/I/RTD 4xM12 (6ES7144-5KD00-0BA0)
Manual, 08/2018, A5E32350124-AD
Measurement type and measuring ranges
Measuring range
1 V to 5 V
0 V to 10 V
0 mA to 20 mA
4 mA to 20 mA
4 mA to 20 mA
150 Ω, 300 Ω
Pt 100 climatic
range/
Pt 100 standard
range
Ni 100 climatic
range/
Ni 100 standard
range
Temperature coefficient Resolution
Pt 0.003850,
Pt 0.003916,
Pt 0.003902,
Pt 0.003920,
Pt 0.003851 EN 60751
Ni 0.006180,
Ni 0.006720
4
max. 16-bit
max. 16-bit
max. 16-bit
max. 15-bit
max. 16-bit incl. sign
max. 16-bit incl. sign
19

Advertisement

Table of Contents
loading

Table of Contents