Units should be elevated 3-12 inches above the pad or rooftop,
depending on local weather. This additional height will allow
drainage of snow and will permit condensate water to drain
when the unit is in defrost mode. Ensure that drain holes in
unit base pan are unobstructed, preventing drainage of defrost
water (See Fig.9).
If possible, avoid locations that are prone to snow drifts. If not
possible, a snow drift barrier should be installed around the
unit to prevent a build-up of snow on the sides of the unit.
  E nsure that Condensate Drain side is pitched lower than the
opposite side.
Condensate drain side
Figure 6
Avoid Install
Near Bedrooms
Min. 24"
Access Panel
Figure 7
  A minimum clearance of 24" should be maintained adjacent to
all access/service panels. Refer to local code requirements for
additional clearance requirements.
BTC 761701105 A | 03.2019
0
h≤ 25mm(1°)
Min. 60" Unrestricted
Min. 24"
Access Panel
Bosch Inverter Ducted Packaged Heat Pump | 11
Min. 24"
Access Panel
Figure 8
Min 24"
Snow
barrier
Figure 9
Corrosive Environment
Exposure to a corrosive environment may shorten the life of the
equipment, corrode metal parts, and/or negatively aff ect unit
performance. Corrosive elements include, but are not limited to: sodium
chloride, sodium hydroxide, sodium sulfate, and other compounds
commonly found in ocean water, sulfur, chlorine, fl uorine, fertilizers, and
various chemical contaminants from industry/manufacturing plants. If
installed in areas which may exposed to corrosive environments, special
attention should be given to the equipment placement and maintenance.
Lawn sprinklers/hoses/waste water should not spray directly
on the unit cabinet for prolonged periods of time.
In coastal areas: locate the unit on the side of the building or
roof away from the waterfront.
Fencing or shrubbery may provide some shielding protection
to the unit, however minimum unit clearances must still be
maintained.
Every three months, wash the outdoor coil and any exposed
cabinet surfaces.
Min. 12" to
Shrubbery
Supply Air Duct
Snow legs
3- 12" Elevation