Download Print this page

Siemens RDG1 series Operating page 8

With lcd for wall mounting
Hide thumbs Also See for RDG1 series:

Advertisement

Disposal
Technical data
RDG100... / RDG110
Power supply
Outputs
Inputs
RDG140 / RDG160
Power supply
Outputs
Inputs
8/12
Siemens
Building Technologies
The device is classified as waste electronic equipment in terms of the European Direc-
tive 2002/96/EC (WEEE) and should not be disposed of as unsorted municipal waste.
The relevant national legal rules are to be adhered to. Regarding disposal, use the
systems setup for collecting electronic waste.
Observe all local and applicable laws.
Operating voltage
Frequency
Power consumption
Fan control Q1, Q2, Q3 - N
Rating
Control outputs
Y1, Y2, Y3, Y4-N (RDG100)
Y11-N / /Y21-N (NO) (RDG110)
Multifunctional inputs
X1-M / X2-M
Temperature sensor input
Type
Digital input
Operating action
Contact sensing
Insulation against mains
D1-GND
Operating action
Contact sensing
Insulation against mains
Function input
External temperature sensor, changeover sensor,
operating mode switchover contact, dewpoint monitor
contact, enable electrical heater contact, fault contact
Operating voltage
Frequency
Power consumption
Fan control
Q1, Q2, Q3 - N (RDG140)
Y50-G0 (RDG160)
Control outputs Y10-G0 / Y20-G0
Resolution
Current
Multifunctional inputs
X1-M / X2-M
Temperature sensor input
Type
Digital input
Operating action
Contact sensing
Insulation against mains
D1-GND
Operating action
Contact sensing
Insulation against mains
Function input:
RDG1... room thermostats
AC 230 V + 10/-15%
50/60 Hz
Max. 18 VA
AC 230 V
Max. 5(4) A
AC 230 V, max. 1 A
AC 230 V, max. 5(3) A
QAH11.1 (NTC)
Selectable (NO/NC)
DC 0...5 V, max. 5 mA
N/A, mains potential
Selectable (NO/NC)
SELV DC 6...15 V, 3...6 mA
3.75 kV, reinforced insulation
Selectable
SELV AC 24 V ± 20%
50/60 Hz
Max. 2 VA
AC 230 V, max. 5(4) A
SELV DC 0...10 V
Max. ± 1mA
SELV DC 0...10 V
39 mV
Max. ± 1 mA
QAH11.1 (NTC)
Selectable (NO/NC)
DC 0...5 V, max. 5 mA
3.75 kV, reinforced insulation
Selectable (NO/NC)
SELV DC 6...15 V, 3...6 mA
3.75 kV, reinforced insulation
Selectable
N3181en