8.4 Compliance

FCC Compliance
This equipment has been tested and found to comply with the limits
for a Class A digital device, pursuant to Part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area is likely
to cause harmful interference in which case the user will be required to
correct the interference at his own expense.
NOTICE: HARMFUL INTERFERENCE HAZARD
Changes or modifications not expressly approved
by the responsible party for compliance could void
the user's authority to operate the equipment.
CE Compliance
NOTICE: HARMFUL INTERFERENCE HAZARD
This is a Class A product. In a domestic
environment, this product may cause radio
interference in which case the user may be
required to take adequate measures.
BTC 469503103 A | 02.2019
Control Air M/M+ Water to Water Applications | 13
External sensor resistance requirements
Temp (°C)
Temp (°F)
-40
-35
-30
-25
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
Table 6
Resistance (Ohms)
-40
335,651
-31
242,195
-22
176,683
-13
130,243
-4
96,974
5
72,895
14
55,298
23
42,315
32
32,651
41
25,395
50
19,903
59
15,714
68
12,494
77
10,000
86
8,056
95
6,530
104
5,325
113
4,367
122
3,601
131
2,985
140
2,487
149
2,082
158
1,752
Data subject to change