6.5 Battery

Batteries and their installation must conform to USCG
Regulations 183.420 (a) through (g). Provide generator
sets with batteries separate from the propulsion
engine's whenever possible.
systems of both the generator set and the engine must
have a common negative (--) ground.
USCG Regulation 183.415, Grounding, requires
connection of a common conductor to each grounded
cranking-motor circuit. Size the conductor to match the
larger of the engine's two battery cables. Figure 6-5 lists
cable sizes for generator set battery connections at
various ambient temperatures. Connecting a common
conductor to each grounded cranking motor circuit
prevents the starting motor current from using
alternative electrical paths should the cranking motor
ground circuit be restricted or open because of oxidation
or loose hardware. Alternative electrical paths include
metallic fuel lines that can pose a fire hazard. See
Figure 6-7 and Section 7 for battery connections to the
generator set.
Distance between
Distance between
At –18°C
Generator Set
(0°F)
and Battery m (ft.)
12.2
(40)
9.1
(30)
7.6
(25)
6.1
(20)
4.6
(15)
3.0
(10)
1.5
(5)
0.8
(2.5)
Figure 6-5 Battery Cable Sizes
Kohler Co. recommends using one 12-volt or 24-volt
battery (as the spec requires) to start the generator. See
Figure 6-6 for minimum cold cranking amps (CCA)
recommendations.
12-Volt Starting Battery Size CCA
at - -18°C (0°F) or 100 Amp. Hr.
Models
3.5–20EFOZ and
4--24EOZ
23/27/100/125EFOZ and
28/32/125/150EOZ
33--80EFOZ and
40--99EOZ
Figure 6-6 Battery Recommendations
24
Section 6 Electrical System
The starting/charging
Cable Size (AWG)
At 0°C
At 24°C
(32°F)
(75°F)
00
0
1
0
1
2
1
2
4
2
2
6
2
4
6
4
6
8
6
6
8
8
8
8
CCA
500
800
640
5
4
1. Starter solenoid
2. Battery positive (+) connection
3. Equipment ground
4. Battery negative (--) connection
5. Engine block mount
Figure 6-7 Battery Connections (5EOZ/4EFOZ
model shown)

6.6 Wiring

Use only stranded copper wire. Conform to USCG
Regulations 183.425 through 183.460 for wire gauges
and insulation, conductor temperature ratings, sheath
stripping, conductor support and protection, conductor
terminals and splices, and over-current protection
(circuit breakers, fuses). Use rubber grommets and
cable ties as necessary to protect and secure the wire
from sharp objects, the exhaust system, and moving
parts.