11. Detailed Settings in EEPROM of Outdoor
Unit
Never use the DN code unlisted in the following table.
DN
Outdoor unit capacity
81
(Setting when the data is not stored in the EEPROM.
Do not change under normal conditions.)
8F
High static pressure setting
1
A3
The minimum operating time 1 until defrosting
A6
Defrost fan speed select
A7
The minimum operating time 3 until defrosting
C1
O
output change
2
CA The defrost detection temperture setting
Discharge air temperature control with thermostat OFF
E1
additional time
EF
Indoor unit auto restart setting
Item
1 - 34
Control Functions - Outdoor unit
Setting No.
0=Invalid
15=112
0=Invalid (P)
1=High static pressure mode 1
(For details, see "4. Outdoor Fan Control (7)")
20=20 minutes
40=40 minutes (P)
(For details, see "8. Defrost Control (2)")
0=Invalid (P) , 1=LL fan speed
0=0 minute ,
90=90 minutes (P) ,,,,,
-1=Invalid
0=Continuously set OFF (P)
1=Refrigerant leak prevention (normal OFF)
2=Refrigerant leak prevention (normal ON)
3=Pumpdown control
(For details, see "3. Special Control (3)")
-3=-3°C (P) , -6=-6°C , -9=-9°C ,,,,, -30=-30°C
-20=-20 minutes
0=0 minute (P) ,,,,,
(For details, see "5. Outdoor Unit CCU Control (5)")
0=No control
1=capable of auto restart
2=incapable of auto restart
Mini VRF SYSTEM
(P) : Factory preset mode
17=140
18=160
21=21 minutes ,,,,,
41 - 90=Never use
10=10 minutes ,,,,,
120=120 minutes
-19=-19 minutes ,,,,,
10=10 minutes