Thermistors - Daikin RMKS112LV1A Service Manual

11.2/14.0/16.0 kw class 48000 btu/h class
Table of Contents

Advertisement

Si181296_A
1.4

Thermistors

Warning
Step
1
For the details of the
removal of the outdoor
temperature thermistor
(R1T), see the points
on the right column.
2
Pull out the discharge
pipe thermistor (R2T).
Suction pipe thermistor 2 (R5T)
Discharge pipe thermistor (R2T)
3
Pull out the suction pipe
thermistors (R3T)
(R5T).
4
Pull out the subcooling
thermistor (R6T) and
the liquid pipe
thermistor (R7T).
5
Pull out the outdoor
heat exchanger
thermistor (R4T).
Removal Procedure
Be sure to wait for 10 minutes or more after turning off all power supplies before
disassembling work.
Procedure
Liquid pipe thermistor
(R7T)
Subcooling
thermistor (R6T)
Suction pipe
thermistor 1 (R3T)
Outdoor heat exchanger
thermistor (R4T)
(R12975)
Outdoor Unit
Points
Removal of the outdoor
temperature thermistor
(R1T)
Hooks (2 places)
Right side panel
Notch
Fixing plate for thermistor (R1T)
Stopper
Removal
direction
Outdoor temperature thermistor
Marking (yellow)
(R13061)
When reassembling, pass
the outdoor temperature
thermistor through the hole
so as the yellow marking
comes to the inside edge of
the heat exchanger plate.
13