Siemens SIMEAS-T 7KG6111-2LK11-0B Operating Instructions Manual page 18

Transducer without auxiliary power for alternating current/alternating voltage/alternating voltage with expanded end range, compact device for din rail mounting
Table of Contents

Advertisement

SIMEAS-T - Transducer without auxiliary power
Calibration of the voltage transducer
Start value
Feed U
= 0.2 U
± 0.05% U
E
EN
I
= 0.2 I
± 0.2% I
A
AN
AN
Full-scale value
Feed U
= U
± 0.05% U
E
EN
potentiometer "max".
Repeat start and full-scale value calibration until the specified tolerances are achieved.
Calibration of the voltage transducer with suppressed start range and expanded
end range
Example: Transducer with range
0 to 0.8 to 1.2 U
= 0 to 0 to I
EN
Start value
Feed U
= 0.8 U
± 0.05% U
E
EN
potentiometer "min".
Full-scale value
Feed U
= 1.2 U
± 0.05% U
E
EN
potentiometer "max".
Check start and full-scale values, repeat calibration if necessary.
To set the potentiometer, refer to the previous schematic diagram.
18
, with trim potentiometer "min" set the output value
EN
.
, set the output end value I
EN
AN
, set the output value I
EN
, set the output value I
EN
= I
± 0.2% I
with trim
A
AN
AN
= 0 + 0.1% I
with trim
A
AN
= I
± 0.1% I
with trim
A
AN
AN