Error Indication; Specifications - Panasonic FX-550L Series Instruction Manual

Digital fiber sensor amplifier for io-link

Advertisement

13

ERROR INDICATION

● In case of errors, attempt the following measures.
Error
Description
indication
Non-volatile memory is broken or reached the end of its
working life.
Non-volatile memory writing error
Load of the sensing output is short-circuited causing an
over-current to flow.
14

SPECIFICATIONS

Type
Discrete wire type
Model No.
FX-551L3-P-C2
Supply voltage
Normal operation: 960mW or less (current consumption 40mA or less at 24V supply voltage)
Power consumption
Eco mode: 720mW or less (current consumption 30mA or less at 24V supply voltage)
IO-Link communication
(C/Q) (Notes: 1)
Baud rate
Process data length
PNP open-collector transistor
Control outputt
• Maximum source current: 50mA
(DO) (Notes: 2)
• Applied voltage: 30V DC or less (Between sensing output and +V)
• Residual voltage: 2V or less (Notes: 3) [At 50mA source current]
Output operation
Short-circuit protection
Response time
STD: 250μs or less, LONG: 2ms or less, U-LG: 4ms or less, HYPR: 24ms or less, Selectable
(Notes: 4)
Interference revention
function
(Functions at emission frequency 1, 2, 3 or 4) (Notes: 5)
Ambient environment
resistance setting
Protection
Over voltage category
Degree of pollution
Operating altitude
Ambient temperature
-10 to +55°C (when 4 to 7 units are installed: -10 to +50°C, when 8 to 16 units are
(Note 7)
installed: -10 to +45°C) (No dew condensation or icing allowed), Storage: -20 to +70°C
Ambient humidity
Material
Enclosure: Polycarbonate, Key: Polyacetal, Protective cover: Polycarbonate
2
Cable
0.2mm
4-core cabtire cable (2 m)
Weight (Main body only)
Approx. 55 g
Notes: 1) For the IO-Link communication setting, refer to the attached sheet, "Index List."(IMJE-FXLINDEX)
2) When the product is used as a general-purpose sensor, the IO-Link communication (C/Q) is generated in the
same way as control output (DO).
3) This value is applicable when the cable length is 2 m.
4) Response time varies depending on the emission frequency setting. Regarding the response time in the case
"
" or "
" is selected, refer to <PRO3> in "
5) When the interference prevention function is used, hysteresis increases. Before using this function, check the
detection conditions.
6) Do not use or store in an environment pressurized to atmospheric pressure or higher at an altitude of 0m.
7) The number of units installed is applicable when units are installed close to each other.
15
CAUTIONS
● This product has been developed / produced for industrial use only.
● Make sure that the power supply is OFF while adding or removing the amplifi ers.
● Take care that if a voltage exceeding the rated range is applied, or if an AC power
supply is directly connected, the product may get burnt or be damaged.
● Take care that short-circuit of the load or wrong wiring may burn or damage the
product.
● Do not run the wires together with high-voltage lines or power lines, or put them in
the same raceway. This can cause malfunction due to induction.
● The specifi cation may not be satisfi ed in a strong magnetic fi eld.
● Verify that the supply voltage variation is within the rating.
● If power is supplied from a commercial switching regulator, ensure that the frame
ground (F.G.) terminal of the power supply is connected to an actual ground.
● In case noise generating equipment (switching regulator, inverter motor, etc.) is
used in the vicinity of this product, connect the frame ground (F.G.) terminal of the
equipment to an actual ground.
● The ultra long distance (U-LG, HYPR) mode is more likely to be affected by
extraneous noise since the sensitivity of that is higher than the other modes. Make
sure to check the environment before use.
● Do not use during the initial transient time after the power supply is switched ON.
● When extending the cable length, use a cable with a conductor cross-sectional
area of 0.3 mm
2
or more. Note that the maximum allowed cable length is 20 m.
However, in order to reduce noise, make the wiring as short as possible.
● Set the power supply voltage by considering the voltage drop resulting from the
conduction resistance of the cable.
● Make sure that the cable joint is not applied with stress, such as strain caused by
forcible bending or pulling.
● This product is suitable for indoor use only.
● Avoid dust, dirt, and steam.
● Take care that the product does not come into contact with organic solvents such
as thinner.
● Take care that the product does not come into contact with strong acids or alkalis.
● Take care that the product does not come into contact with oil or grease.
● This product cannot be used in an environment containing inflammable or
explosive gasses.
● Never disassemble or modify the product.
● This product adopts Non-volatile memory. Settings cannot be done 1 million times
or more because of the Non-volatile memory's lifetime.
Remedy
Please replace the product.
Turn OFF the power and check the load.
M12 connector type
FX-551L3-P-J
12 to 24V DC
+10
% Ripple P-P10% or less
‒15
IO-Link specifi cation: Ver1.1
COM3(230.4kbps)
PD:4byte
Switchable either Light-ON or Dark-ON
Incorporated
Incorporated
Emission frequency selection method
Incorporated
IP40 (IEC)
2
2,000m or less (Notes: 6)
35 to 85% RH, Storage: 35 to 85% RH
2
0.2mm
4-core cabtire cable with M12
connector (0.3m)
Approx. 90 g
PRO MODE."
12
http://panasonic.net/id/pidsx/global
Overseas Sales Division (Head Offi ce)
2431-1 Ushiyama-cho, Kasugai-shi, Aichi, 486-0901, Japan
Phone: +81-568-33-7861 FAX: +81-568-33-8591
For sales network, please visit our website.
PRINTED IN JAPAN
© Panasonic Industrial Devices SUNX Co., Ltd. 2018