5. FR-E5ND SPECIFIC PARAMETERS

There are several parameters which are used only when the FR-E5ND is installed in the FR-E520S-EC/CH or FR-ES40
inverter. The following sections describe these parameters.
5.1 Pr. 345 to Pr. 348
Pr. No.
345
DeviceNet address start-up data (Lower byte)
346
DeviceNet Baudrate start-up data (Lower byte)
347
DeviceNet address start-up data (Higher byte)
348
DeviceNet Baudrate start-up data (Higher
byte)
To support the FR-E5ND, 4 new parameters were created, Pr. 345, Pr. 346, Pr. 347 and Pr. 348.
The PU displays only in decimal integers. The hexadecimal integers in the parentheses are used here for easy bitmap
reference only.
Pr. 345 and Pr. 347 are bit-mapped parameters. There definition is as follows.
15
14
13
12
Address key
Bit 7
6
5
4
Pr. 347
Function
11
10
9
8
EPR
DN fault mode
3
2
1
Bit 0
FR-E5ND SPECIFIC PARAMETERS
Setting range
Minimum increment
0 to 255
0 to 255
0 to 255
0 to 255
7
6
5
4
Device node address
Bit 7
6
5
4
24
Default setting
1
63 (0x3F)
1
132 (0x84)
1
160 (0xA0)
1
80 (0x50)
3
2
1
0
3
2
1
Bit 0
Pr. 345