VARkombi-PC

5.3 ADVANCED MENU

It is the section that important and critical settings of the device can be done.
To avoid accidental access to this menu, it is accessed by energizing the device
while hold down the set button. It is important to hold down the button when the
device is de-energised and energize it while the button is pressed and keep it
pressed till the 'AdU' appears on the screen.
Using the direction keys, can be advanced in the desired direction. To enter any
section, just press set button on it. When set button is pressed on the 'quit' section,
device resets itself and starts in normal mode. Also, when no key is pressed for 4
minutes, device resets itself. In both cases, before reset, device stores the changes
in its memory.
Capacitor Step Number Determination Menu
► CSAY :
It is the section that used to set used
capacitor step number. Capacitor step
number is set in the range of 3-8/12.
Parameter name and capacitor step
number are shown by interchanging on the
screen.
It is advised to set the capacitor step
number to the value that you wish to use.
Penalty Boundary Values Determination Menu
► SIn :
It is the section that penalty boundary values are adjusted in terms of (reactive energy /
active energy) %. It is accessed by pressing the set button. Inductive boundary (CZ-E) and
capacitive boundary (CZ-C) are accessed by direction keys. Pressing down the set button,
the one level up menu section is reached. Please do not set boundary values to higher
values than the limits of your power distributer firm.
CZ-E : It is the section that inductive penalty value is set as %. It is accessed by
pressing the set button, the value is adjusted by using the direction buttons and it
is stored by pressing the set button again. It can be set in the range of 10% - 50%
(reactive energy / active energy).
If inductive % is close to penalty limit, inductive value can be set to a lower value
from here.
CZ-C : It is the section that capacitive penalty value is set as %. It is accessed by
pressing the set button, the value is adjusted by using the direction buttons and it
is stored by pressing the set button again. It can be set in the range of 5% - 50%
(reactive energy / active energy).
If capacitive % is close to penalty limit, capacitive value can be set to a lower
value from here.
quit : Pressing down the set button, device returns to main menu.
8
when the device is de-energised
and energize it while the button is
pressed and keep it pressed till
the 'AdU' appears on the screen.
+
-
Capacitor Step Number
Determination Menu
Penalty Boundary
Values Determination
Menu
Current Transformer
and Capacitor Bank
Power Setting Menu
Clearing Capacitor
Bank Power Menu
Alarm Set Menu
Cihaz
Number of device for
Numarası
communication
Factory Settings Menu
Pressing down
the set button,
device returns
to main menu.
+
-
+
-