1MRS756125
4.3.5.2.
COM600 Station Automation Series
User's Guide
Figure 4.3.5.1-1 An example of creating event classes
Configuring event definitions
You can configure event definitions in Communication Engineering Tool (CET). Event
definitions specify the type of events that are created for HMI event and alarm lists. You
can specify whether an event appears only on the event list, on both event and alarm
lists, or whether it is displayed at all. You can also add event texts for the events and
specify whether alarms have to be acknowledged by the user.
Event definitions are linked to data objects by configuring the event properties available
for data objects. When importing IED configurations from connectivity packages or IED
SCL description files, event definitions are linked to data objects by default. For example
switch position data object CSWIx.Pos is linked by default to switch position event
definition. The default linking rules are specified in a DOParamsDefaults.xml file located
in the \Program files\ABB\COM600\bin\Tools\SCLImport in the computer where CET
is installed.
To configure event definitions:
1. Select the event you want to configure in the object tree.
2. The object properties appear now in the Object Properties window, see Figure 4.3.5.2-
1.
3. You can assign the event with parameter values.
Table 4.3.7.3-1 lists the available scales.
COM600 3.2
creating_events.jpg
41