Download Print this page
Danfoss KPU Series Installation Manual

Danfoss KPU Series Installation Manual

Pressure switch

Advertisement

Quick Links

Installation guide

Pressure switch
KPU
Application
KPU pressure switches are for use on commercial
refrigeration and air conditioning systems to give protection
against excessively low suction pressure or excessively
high discharge pressure.
They are also used for starting and stopping refrigeration
compressors and fans on air-cooled condensers.
KPU pressure switches are fitted with the Single-Pole Single-
Throw (SPST) or Single-Pole Double-Throw (SPDT) switches,
suitable for direct as well as indirect (with a contactor) control.
KPU pressure switches are available in several pressure ranges
and are compatible with refrigerants listed below. KPU 6W and
KPU 6B are fail safe switches for high pressure refrigerants.
Standard enclosure is ~NEMA 1.

Product Specification

Application
Type
¼ in
male flare
KPU 1
060-5231
KPU 1
060-5236
Low Pressure
Switch Cut Out
KPU 2
060-5237
on pressure
fall
KPU 2
060-5239
KPU1B
060-5232
Fan switch
KPU 5
060-5241
High Pressure
KPU 6W
060-5243
Switch
Cut Out on
KPU
060-5244
pressure rise
6B
* 610psig - MWP for products used according to 97/23/EG PED directive.
Installation
Select an accessible location, where the switch and pressure connection line will not be subject to damage.
© Danfoss | DCS (jmn) | 2016.11
Code number
36 in. cap.
Reset
tube w. ¼
in flare nut
060-5233
Auto.
Auto.
060-5235
Auto.
060-5240
Auto.
060-5234
Man (Min.)
060-5242
Auto.
060-5245
Auto.
060-5246
Man. (Max.)
Refrigerants:
R22, R134a, R404A, R407A, R407C, R407F, R410A*), R422B,
R422D, R438A, R448A, R449A, R450A, R452A, R507A, R513A
For complete list of approved refrigerants, go to
http://products.danfoss.com/all-products/
*) R410A only for KPU 6W and KPU 6B
Contact system
Switch
Type
action
SPDT
SPST(NO)
close High open Low
SPST(NO)
close High open Low
SPDT
SPDT
SPST(NO)
close High open Low
SPDT
SPDT
IMPORTANT:
Mount the pressure switch in a position that
will allow drainage of liquids away from switch
bellows. Pressure connection of the switch
must always be located on the top side of the
refrigerant line.
This reduces the possibility of oil, liquids, or
sediment collecting in the bellows, which could
cause the switch malfunction.
IMPORTANT:
Ensure the ambient temperature for the pressure
switch is higher than the refrigeration line as that
will prevent liquid migration and accumulation in
the bellows.
Max.
Regulating
Differential
working
range
∆p
pressure
[inHg] [psig]
[psi]
[psig]
6 in. – 108
10 – 60
250
6 in. – 108
10 – 60
250
6 in. – 73
6 – 30
250
6 in. – 73
6 – 30
250
28 in. – 100
10 fixed
250
100 – 465
25 – 85
510
100 – 600
58 – 145
675 / 610*
100 – 600
60 fixed
675 / 610*
DKRCC.PI.CD0.F4.22 | 520H11543 | 1
Max.
Ambient
testing
temp.
pressure
[psig]
[°F]
290
290
290
-40 – 122
290
(175 for
290
max.
2 hours)
530
725
725

Advertisement

loading

Summary of Contents for Danfoss KPU Series

  • Page 1: Installation Guide

    IMPORTANT: Ensure the ambient temperature for the pressure switch is higher than the refrigeration line as that will prevent liquid migration and accumulation in the bellows. DKRCC.PI.CD0.F4.22 | 520H11543 | 1 © Danfoss | DCS (jmn) | 2016.11...
  • Page 2 Do not exceed tightening torque 20 lb. in (2.3 Nm). Do not exceed electrical ratings for the switch. The terminal block as well as grounding screw are accessible after dismounting of the front cover. 2 | 520H11543 | DKRCC.PI.CD0.F4.22 © Danfoss | DCS (jmn) | 2016.11...
  • Page 3 Do not adjust pointers beyond the highest or lowest to push the reset knob. indicator marks on the scale plate, as this may cause inaccurate switch operation. DKRCC.PI.CD0.F4.22 | 520H11543 | 3 © Danfoss | DCS (jmn) | 2016.11...
  • Page 4 Scale plate directly indicates the Cut Out set point. There is no pointer for the Differential. The Differential pressure value is fixed and printed on the scale plate. 4 | 520H11543 | DKRCC.PI.CD0.F4.22 © Danfoss | DCS (jmn) | 2016.11...

This manual is also suitable for:

Kpu 1bKpu 5Kpu 6wKpu 1Kpu 6bKpu 2 ... Show all