LG MULTI V Installation Manual page 33

R410a refrigerant
Hide thumbs Also See for MULTI V:
Table of Contents

Advertisement

Ú Refrigerant pipe diameter from branch to branch (B,C,D)
Downward Indoor Unit total capacity
[kW(Btu/h)]
≤ 5.6(19,100)
< 16.0(54,600)
≤ 22.4(76,400)
< 33.6(114,700)
< 50.4(172,000)
< 67.2(229,400)
< 72.8(248.500)
< 100.8(344,000)
< 173.6(592,500)
< 184.8(630,700)
< 224.0(764,400)
Ú Total pipe length = A+B+C+D+a+b+c+d+e ≤ 3281ft(1000m)
Longest pipe length
L
A+B+C+D+e ≤ 492ft(656ft**(200m))
Longest pipe length after 1st branch
B+C+D+e ≤ 131ft**(40m))
Difference in height(Outdoor Unit ÷ Indoor Unit)
H
H ≤ 361ft(110m)
Difference in height (Indoor Unit ÷ Indoor Unit)
h
h ≤ 49ft(15m)
Difference in height (Outdoor Unit ÷ Outdoor Unit)
h1
h1 ≤ 16.4ft(5m)
• * : Assume equivalent piping length of Y branch to be 1.6ft(0.5m), that of header to be 3.3ft(1m), calculation
purpose.
• ** : To apply Conditional Application
WARNING
If overall equivalent pipe length is greater than or equal to 295ft(90m) from ODU to the longest IDU,
The diameter of the main pipe (Gas and Liquid pipes) must be increased as follow.
Ú Refrigerant pipe diameter from outdoor unit to first branch. (A)
Outdoor unit
Total capacity
[kW (Btu/h)
16.0~22.4(54,600~76,400)
28.0(95,900)
33.6~44.8(172,000~152,900)
50.4~61.6(172,000~210,600)
67.2(229,400)
72.8~95.2(248,500~324,900)
100.8~168.0(344,000~573,300)
173.6~179.2(592,500~611,600)
184.8~224.0(630,700~764,400)
h If the step up size is not available, you can not select the next higher size available.
Pipe connections between indoor and outdoor unit
Liquid pipe
[inch(mm)]
1/4(Ø6.35)
3/8(Ø9.52)
3/8(Ø9.52)
3/8(Ø9.52)
1/2(Ø12.7)
5/8(Ø15.88)
5/8(Ø15.88)
3/4(Ø19.05)
3/4(Ø19.05)
7/8(Ø22.2)
7/8(Ø22.2)
Equivalent pipe length
*A+B+C+D+e ≤ 574ft(656ft**(200m))
Standard Pipe Diameter
Liquid pipe
Gas pipe
[mm (inch)]
[mm (inch)]
19.05(3/4)
9.52(3/8)
22.2(7/8)
12.7(1/2)
28.58(1 1/8)
15.88(5/8)
34.9(1 3/8)
19.05(3/4)
41.3(1 5/8)
44.5(1 3/4)
22.2(7/8)
53.98(2)
Gas pipe
[inch(mm)]
1/2(Ø12.7)
5/8(Ø15.88)
3/4(Ø19.05)
7/8(Ø22.2)
1
1
/
( Ø28.58)
8
1
1
/
(Ø28.58)
8
1
3
/
(Ø34.9)
8
1
3
/
(Ø34.9)
8
5
1
/
(Ø41.3)
8
1
3
/
(Ø44.5)
4
2(Ø53.98)
Conditional application
(more than 90m from ODU to IDU)
Liquid pipe
Gas pipe
[mm (inch)]
[mm (inch)]
12.7(1/2)
15.88(5/8)
28.58(1 1/8)
31.8(1 1/4)
19.05(3/4)
34.9(1 3/8)
38.1(1 1/2)
22.2(7/8)
41.3(1 5/8)
25.4(1)
Installation Manual 33
22.2(7/8)
25.4(1)
53.98(2)

Advertisement

Table of Contents
loading

Table of Contents