4.1.4
Parameters of the Counting mode
Parameters of the DI 16x24VDC HF Count in the Counting mode
If you want to use the module for counting, you need to set the module parameters as
DI 16x24VDC HF Count. For channels 0 and channel 1, the following parameter settings are
then possible. For channels 2 to 15, the parameter settings apply as with the
DI 16x24VDC HF, , see section Parameters DI mode (Page 17).
Table 4- 2
Settable parameters and their defaults in the Counting mode
Parameter
Diagnostics
No
•
supply voltage L+
Wire break
•
Input delay
Hardware interrupt
Set output DQ
Edge selection
High counting limit
DI 16x24VDC HF Digital Input Module (6ES7521-1BH00-0AB0)
Manual, 08/2018, A5E03485952-AG
Range of values
Yes/No
Yes/No
0.05 ms, 0.1 ms, 0.4 ms,
1.6 ms, 3.2 ms, 12.8 ms,
20 ms
Disable
•
Comparison event oc-
•
curred for DQ
Between a comparison
•
value and the high count-
ing limit
Between a comparison
•
value and the low count-
ing limit
On rising edge
•
On falling edge
•
On rising and falling
•
edge
0 ... 4294967295
Default
Parameter
setting
reassignment
in RUN
No
Yes
No
Yes
3.2 ms;
Yes
for isoch-
ronous
mode
0.05 ms
(cannot
be
changed)
Disable
Yes
Between
Yes
a compar-
ison value
and the
high
counting
limit
On rising
Yes
edge
42949672
Yes
95
Parameters/address space
4.1 Parameter
Range of effectiveness with con-
figuration software, e.g. STEP 7
Integrated in the
GSD file
hardware catalog
PROFIBUS DP
as of STEP 7,
V13 SP1 with
HSP 0118 or
GSD file
PROFINET IO
Channel*
---
Channel
---
Channel
---
Channel
---
Channel
---
Channel
---
Channel
---
19