Enclosure; Configuration; Certification And Approvals - Honeywell Apex Technical Handbook

Gas detection system
Hide thumbs Also See for Apex:
Table of Contents

Advertisement

MAN0604_Issue 09_02-2013
2110M8030
APPENDIX A - SPECIFICATIONS
A.1.8 Enclosure
Physical:
Size:
Weight:
Mountings:
Ingress Protection
(Transmitter Unit with
Certified Sensor fitted)
A.1.9 Configuration
The Transmitter Unit can be configured during installation and operation to accept any of the
Certified Sensors it is compatible with (see the gas/cartridge tables in section A.2).
A.1.10 Certification and Approvals
Hazardous Area Certifications
Transmitter Unit:
ATEX:
UL:
CSA:
Transmitter Unit Certified to CSA C22.2 No. 152 only when Certified Sensor is fitted with specific
The Transmitter Unit has:
One threaded hole in the base for mounting the Certified Sensor
- M20 (European) or 3/4" NPT (North American versions)
Two threaded holes in the base to accept two certified M25 cable
glands (European) or two 3/4" NPT conduit fittings (North American
versions).
Provision is made to attach a tag carrying an ID number.
The enclosure materials for Apex are electro-polished grade 316
stainless steel (to BS3146 ANC 4B FM/BS3146 ANC 4C FM) and
Zinc Alloy.
140mm wide x 150mm high x 152mm deep.
4000gm.
Provision for two M10 bolts, centres 68mm apart.
IP67 to BS EN 60529:1992, Degrees of protection provided by
enclosures (IP code).
II 2 G D Ex d ia IIC Ex tD A21 IP67
Operating temperature codes:
T135°C (Tamb -40 to +80°C)
T100°C (Tamb -40 to +55°C)
Baseefa08ATEX02523
Approvals by UL
Class I, Division 1, Groups B, C, D
Operating temperature codes:
T4 (Tamb -40 to +80°C)
T5 (Tamb -40 to +55°C)
Approvals by CSA
Class I, Division 1, Groups B, C, D
T4 (Tamb -40 to +75°C)
T5 (Tamb -40 to +55°C)
cartridges. See A.2 Cartridges, Flammable SG16 - US/Rest of the
world version (page 108 ).