Page 1
Introduction Additional Information EBS852 EBS862 The electronic unit builds the interface between Additional documentation on EBS852 / EBS862 is the actuator and the control system. available for download free of charge at During continuous positioning, the electronic unit www.abb.com/actuators. varies the motor torque continuously until the...
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B Table of contents Change from one to two columns Commissioning and operation ......30 Safety ................3 General information and instructions ........3 General information .............. 30 ...
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B Change from one to two columns 1 Safety Warnings General information and instructions The warnings in these instructions are structured as follows: These instructions are an important part of the product and must be retained for future reference.
Intended use Using the device in a manner that does not fall within the scope The electronic units of type EBS852 / EBS862 interconnected as of its intended use, disregarding this manual, using illustrated in this operating instruction are used exclusively to underqualified personnel, or making unauthorized alterations control the RHDE...
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B 2 Use in potentially explosive atmospheres Cable harness for the connection of the DANGER actuator to the electronic unit Explosion hazard due to improper installation! An explosion hazard is present when installing the electronic Installation information on the cable harness for actuators in unit in potentially explosive atmospheres.
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B … 2 Use in potentially explosive atmospheres … Cable harness for the connection of the actuator to the electronic unit Specification Motor connection Motor temperature monitoring Signal terminal (option) Wire conductor 8 ×...
Page 7
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B Option Motor connection Motor temperature monitoring Signal terminal (option) Manufacturer Pflitsch Pflitsch Type blue globe ATEX blue globe ATEX Diameter M25 × 1.5 KAD20-16/16-11 M20 × 1.5 KAD14-9/9-5 Article no. bg225 msex...
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B … 2 Use in potentially explosive atmospheres Overview Figure 1: Allocation of the Contrac components when using in potentially explosive atmospheres (example) Change from one to two columns Change from one to two columns...
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B 3 Design and function Design EBS852 EBS862 M10450 1 Electronic unit cover 7 Ground terminal 1 Commissioning and service field 6 Terminals (power supply) 2 Lifting eye 8 Terminals (power supply)
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B … 3 Design and function Principle of operation The electronic unit builds the interface between the actuator and the control system. During continuous positioning, the electronic unit varies the motor torque continuously until the actuator force and the control valve force are balanced.
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B Device designs EBS852 IP rating IP 20 Humidity ≤ 75 % annual average; condensation not permitted Rack air inlet temperature 0 to 45 °C (32 to 113 °F) Transport and storage temperature −25 to 70 °C (−13 to 158 °F)
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B 4 Product identification Note In electronic units which can be separated for assembly, the Elektronik / Electronics Type: ... name plate for the hardware is located on the lower part of the B-Nr./No.
Action after restoration of Switch to Automatic Storing the device power The electronic units EBS852 / EBS862 comply with IP rating IP 20. Working range of actuator Not set The electronic units should be stored in accordance with this IP rating.
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B 6 Installation Mounting When installing the electronic unit, observe the following points: NOTICE • You must be able to activate the power supply of the Damage to components! electronic unit on-site.
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B EBS862 Assembly and cable routing in the mounting rack Note When installing the electronic units in a mounting rack (on site), The total weight of the electronic unit is 40 kg (88 lbs). For this...
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B 7 Electrical connections Safety instructions General Each actuator requires a suited Contrac electronic unit with WARNING installed actuator-specific software. Observe the information in Risk of injury due to live parts! the operating instruction. The specifications on the name plates...
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B … 7 Electrical connections Conductor cross-section on electronic unit Note Tap holes for cable glands Detailed information on separate electronic units can be found metric in the corresponding data sheets. Power supply M20 ×...
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B Please observe the following information when installing the Scenario 1 cable set: If the PE of the actuator is done only via the PE conductor of the • The specific regulations governing the installation of...
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B … 7 Electrical connections Actuator assignment and maximum cable lengths Rotary actuators Electronic unit Actuator Cross-section of the motor cable / maximum permissible cable length* 1.5 mm (16 AWG) 2.5 mm...
Page 23
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B Electronic unit EBS852 (Contrac) / EBS862 (Contrac) Note • The electrical connection is established via screw terminals on the control actuator and on the electronic unit. • If you are using a separate heat supply, the heater must be protected with a 2 to 6 A medium time-lag fuse (e.g. NEOZED D01 E14).
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B … 7 Electrical connections Connection examples Operation following a continuous set point (standard) In the standard configuration, the binary inputs are configured as ‘MANUAL OPERATION’. To switch the actuator to automatic mode (AUT), the following conditions must be met: •...
Page 25
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B Operation downstream from step controller Contrac actuators can be driven using step controller pulses instead of an analog setpoint. The following conditions must be fulfilled in order to implement the step controller pulses: •...
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B … 7 Electrical connections Electrical data for inputs and outputs Power supply EBS852 Supply voltage (standard actuators) 115 V AC (94 to 130 V) or 230 V AC (190 to 260 V); 47.5 to 63 Hz; single-phase Supply voltage (Ex actuators) 115 V AC (94 to 127 V) or 230 V AC (190 to 253 V);...
Page 27
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B Binary inputs and outputs - communication Conventional communication Analog input 0 / 4 to 20 mA, internal load: 300 Ω Analog output 0 / 4 to 20 mA, electrically isolated, maximum load: 500 Ω...
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B … 7 Electrical connections … Electrical data for inputs and outputs Connection on the device EBS852 Power supply Observe the following points when connecting the power supply: Power • You must be able to activate the power supply of the electronic unit on-site.
Page 29
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B EBS862 Connection of cable shielding M10307 1 Cable clip 3 Shielding 2 Cable sheath 4 Housing Figure 17: Cable shielding 1. Remove the cover for the terminal compartment. 2. Cut the cable sheath to the required length.
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B 8 Commissioning and operation Engineering Software ECOM688 and ECOM700 Note It is imperative that you observe the operating instruction of the Using the ECOM688 / ECOM700 engineering software, the user corresponding actuator for the commissioning of the electronic...
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B Commissioning and service field Operating element Description Write protection switch Activates the hardware write protection. Power Factory setting: OFF – write protection deactivated. Refer to Hardware write protection on page 33.
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B … 8 Commissioning and operation … Commissioning and service field Meaning of the LED indicators The LEDs 100 % / 0 % on the commissioning and service field (Figure 18 on page 31, Pos.
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B Hardware settings Hardware write protection Defining the initial position (0 % or 100 %) If write protection is active, the device parameterization cannot 2. Use one of the travel buttons to move to the desired be changed.
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B … 8 Commissioning and operation Manual (MAN)- and Automatic Operation (AUT) Software version 2.00 and higher Signaling on the commissioning and service field In the manual operating mode (MAN), the actuator solely reacts...
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B 9 Diagnosis / error messages Definition – Alarms and Errors Alarms The actuator / electronic unit is in a critical state (e.g., high temperature), which currently does not affect the actuator, electronic unit, process or persons.
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B Hardware Errors This chapter only covers hardware-related errors. For additional troubleshooting information, refer to the online help for the operator interface. Error Possible cause Troubleshooting the Instrument Valve cannot be moved by actuator.
All devices delivered to ABB must be free from any hazardous Contrac actuators feature a robust construction. As a result, materials (acids, alkalis, solvents, etc.).
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B Fuses Type Fuse Installation location Design Rated current of fuse at 115 V AC at 230 V AC EBS852 External fuse External – 16 A, time-lag 16 A, time-lag Mains fuse...
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B 12 Recycling and disposal 13 Approvals and certifications Note CE mark The version of the device as provided by us meets the Products that are marked with the adjacent symbol requirements of the following EU directives: may not be disposed of as unsorted municipal waste •...
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B 15 Appendix Return form Statement on the contamination of devices and components Repair and/or maintenance work will only be performed on devices and components if a statement form has been completed and submitted.
Page 42
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B Trademarks HART is a registered trademark of FieldComm Group, Austin, Texas, USA...
Page 43
EBS852 / EBS862 ELECTRONIC UNIT | OI/EBS852/EBS862/EX-EN REV. B Notes...
Page 44
We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.