Indoor unit Installation
Indoor unit Installation
•
Select a location where air can be distributed to all corners of the room.
•
Make sure no obstruction to return and dischage air.
•
Avoid installation at the following location:
- area where flamable gas may leak or generated.
- places where unit is frequently exposed to corrosive gas, or acidic solutions.
Warning:
•The unit must be securely installed on structure that can sustain its weight.
Service space
•
Make sure sufficient space for service and
maintenance (see figure).
Installing indoor unit
Unit suspension
•
Use the hanging rods to hang the unit through the holes provided. Strength of
hanging rods must be ble to support the total weight of the unit.
•
Add isolator, absorber , if necessary , to minimize the vibration transmission
to the ceiling.
Drain pipe
•
Drain pipe shall be properly installed for the drainage for the drainge
of condensate water.
•
Trap shall be installed (See figure)
•
Make sure no leak at the connecting joint.
•
Insulate the drain pipe to avoid water condensation.
Min. 800mm
Trap