Mounting And Installation; Creating A Zoning Plan - Honeywell HCE80R Mounting And Operation Instructions

Table of Contents

Advertisement

6

Mounting and installation

Creating a zoning plan

Within a building rooms (zones) can be controlled with different room
setpoint temperatures. The thermal actuators of the allocated zone (room)
are controlled depending on the room setpoint temperature.
!
A maximum of 5 temperature zones can be
set up for each underfloor heating controller.
This number can be increased to 8 by
using the expansion module HCS80.
A maximum of 3 thermal actuators
can be connected in each zone.
Specifying temperature zones
Specify the number of zones and
1
the corresponding rooms.
Allocate the corresponding room device,
2
for example HCW82 and the required
thermal actuators to each zone.
Label the room devices and thermal actuators for the
3
respective zone (see fold-out page Fig. 4, Z1...Z8).
Explanation of the example
The living area is covered by six temperature
zones. The additional module HCS80
is required for this partitioning.
The underfloor heating controller
controls 8 thermal actuators.
Mounting and installation
Temperature
zones (maximum)
16
24
Thermal actuators
(maximum)
8
24
48
72
Number of
underfloor heating
controllers
1
2
3