Daikin FTK(X)M-P Series Service Manual page 72

Inverter pair wall mounted type
Table of Contents

Advertisement

Troubleshooting
Troubleshooting
Check No.02
Check the power supply
voltage.
Refer to P.84
Turn off the power and
rotate the fan by hand.
Turn on the power and
start operation.
Note:
The rotation pulse is the feedback signal from the indoor fan motor.
57
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Is the
voltage
NO
fluctuation
within ±10% from
the rated
value?
YES
NO
Does the fan
rotate smoothly?
YES
Turn off the power and
NO
disconnect the fan motor
Does the fan
connector, then turn the
rotate?
power on.
YES
Check No.02
Check the output of the
fan motor connector.
Stop the fan motor.
Check No.02
Check the output of the
fan motor connector.
Indoor fan
NO
motor rotation pulse
generated?
YES
Note: The motor may break when the
Motor
NO
power supply
voltage 310 ~ 340
VDC?
YES
Motor
NO
control voltage 15
VDC generated?
YES
Rotation
NO
command voltage
1 ~ 6.5 VDC?
YES
Indoor fan
NO
motor rotation pulse
generated?
YES
SiMT041509E
Correct the power
supply.
Replace the indoor
fan motor.
motor connector is disconnected
while the power is turned on.
(Be sure to turn off the power
before reconnecting the
connector.)
Replace the indoor
unit PCB (control
PCB).
Replace the indoor
unit PCB (control
PCB).
Replace the indoor
unit PCB (control
PCB).
Replace the indoor
fan motor.
Replace the indoor
unit PCB (control
PCB).
Replace the indoor
fan motor.
Replace the indoor
unit PCB (control
PCB).
Service Diagnosis
(R22444)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents