Figure 26. Types of receptacles for Models of the TS4500 tape library
Note: For more information about FC 9989, refer to Powering adjacent frames.
Electrical characteristics for the TS4500 tape library frame
models
Table 40 lists the electrical characteristics for the TS4500 tape library frame models.
To calculate the total power consumption (in watts) of a particular library
configuration, multiply the quantity of each power-consuming item in the
configuration by the corresponding value in Table 38 on page 93.
Note: Library power consumption is dynamic and usage dependent. Short peaks
might exceed the maximum continuous power values. Typical average power
consumption is lower than the calculated maximum continuous value because all
drives are not likely to be active simultaneously.
Table 40. Electrical characteristics of the TS4500 tape library frame models
Electrical characteristic
Nameplate electrical limits
Notes:
1. Maximum certified electrical limits for a single frame. Do not use nameplate limits to calculate product power or
cooling requirements.
2. Electrical limits increase for frames with FC 1951 because the PDUs for FC 1951 can be used to supply power for
up to two adjacent frames.
96
IBM TS4500: Introduction and Planning Guide
3
7
A
12
Rating (Models Lx5, Dx5)
1
200 - 240 V AC, 8.0 A, 50 - 60 Hz, 1.6
kVA, single phase
4
8
N
13
200 - 240 V AC, 24.0 A, 50 - 60 Hz,
4.8 kVA, single phase
9
Rating (Models xx5 with FC 1951)
2