Maintenance; Troubleshooting - Greenheck ODFD Series Installation, Operation And Maintenance Instructions

11/2 hour combination fire smoke or curtain fire dampers out of wall or out of floor vertical or horizontal mount
Table of Contents

Advertisement

Clip Spacing
6 in.
60 in. Duct
4 Req'd.
7 in.
48 in. Duct
3 Req'd.
5 in.
36 in. Duct
Duct
3 Req'd.
5 in.
24 in. Duct
2 Req'd.
18 in. Duct
&
Smaller
1 Req'd.
Figure 10:
Detail of proprietary flanged system
breakaway connections.
Damper Maintenance
Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild
detergents or solvents. If lubrication is desired for components such as axle bearings, jackshaft bearings and jamb seals, do
not use oil-based lubricants or any other lubricants that attract contaminants such as dust.
Dampers and their actuator(s) must be maintained, cycled, and tested a minimum in accordance with:
• The latest editions of NFPA 80, 90A, 92A, 92B, 101, 105, UL864, AMCA 503-03 and local codes.
• Actuator manufacturer recommendations.
Damper Troubleshooting
The following is a possible cause and correction list for common concerns with the dampers.
Symptom
Damper does not
fully open and/or
close
RRL or TOR sensor
tripped
Damper does not
operate
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without
notice.
Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library
under Warranties.
®
Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: gfcinfo@greenheck.com • Website: www.greenheck.com
461337• ODFD OFD Rev. 14, August 2013
12
Std. Clip
Length
9 in.
6 in.
6 in.
7 in.
5 in.
5 in.
C L
Duct
Possible Cause
Frame is 'racked' causing blades
to bind on jamb seals
Actuator linkage loose
Defective motor
Screws in damper linkage
Contaminants on damper
Heat
No power supplied to the actuator
Duct End
Flange
Figure 11
Corrective Action
Adjust frame such that it is square and plumb
Close damper, disconnect power, adjust and
tighten linkage
Replace
Damper installed too far into wall. Move out
to line as designated on damper label
Clean with a non-oil based solvent (see
Damper Maintenance)
Push reset button located on backside of
RRL or TOR
Add power supply
Copyright 2013 © Greenheck Fan Corporation