1-9. Tubing Length

Select the installation location so that the length and size of refrigerant tubing are within the allowable range shown
in the figure below.
LA
Main tube of unit
1st branch
Unit distribution tube
Note: Do not use commercially available T-joints for the liquid tubing.
* Be sure to use special R410A distribution joints (APR: purchased separately) for outdoor
unit connections and tubing branches.
Table 1-16 Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights
Items
Allowable tubing
length
1
Allowable elevation
difference
L = Length, H = Height
L1
L2
LB
LC
L3
2
3
1
Marks
L1
Max. tubing length
Difference between max. length and min.
L (L2 – L3)
length from the No.1 distribution joint
,
...
Max. length of each distribution tube
1
2
n
Total max. tubing length including length of
+
+...
+L1
2
n–1
each distribution tube (only narrow tubing)
When outdoor unit is installed higher than indoor unit
H1
When outdoor unit is installed lower than indoor unit
H2
Max. difference between indoor units
LD
n
n-1
Contents
Actual length
Equivalent length
12
H1
H2
R410A distribution joint
APR-P160BA (for indoor unit)
Length (ft.)
>
492
>
574
>
131
>
98
>
656
>
164
>
131
>
49