Siemens DAC-NET Installation Instructions Manual page 4

Digital audio card - network
Table of Contents

Advertisement

D-NET
A24205-A334-B839 (Edition 14)
P/N 315-035100-14
ASI FAIL
(Yellow)
CPC-DAC FAIL
(Yellow)
ALARM
(Red)
EXT ALARM TRBL
(Yellow)
_
TRBL
MAIN IN
(Yellow)
RETURN OUT
GND FAULT
(Yellow)
_
TRBL
MAIN OUT
(Yellow)
RETURN IN
GND FAULT
(Yellow)
4
Normally OFF. When illuminated, indicates
that the ASI communication has
terminated.
Normally OFF. When illuminated, indicates
that the communication between PMI/PMI-
2/PMI-3 and DAC-NET has terminated.
Normally OFF. When illuminated, indicates
that the DAC-NET has detected an active
alarm.
Normally OFF. When illuminated, indicates
that the DAC-NET has detected a trouble
on the External Alarm input (open circuit or
short circuit).
Normally OFF. When illuminated, indicates
that the DAC-NET has detected a trouble
on Main In.
Normally OFF. When illuminated, indicates
that the DAC-NET has detected a ground
fault on one of its field wires before the
node.
Normally OFF. When illuminated, indicates
that the DAC-NET has detected a trouble
on Main Out. When blinking twice per
second, indicates that the DAC-NET has
detected a trouble on Return In (open
circuit, short circuit or data trouble).
Normally OFF. When illuminated, indicates
that the DAC-NET has detected a ground
fault on one of its field wires after the
node.
s

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents