Room pressurization controller pneumatic output

Advertisement

Document Number 540-1032
Installation Instructions
May 3, 2017
Table 1. Application Descriptions.
Application
Description
2215
CAV/VAV Room
Pressurization with
Hot Water Reheat
2217
VAV Room
Pressurization with
Hot Water Reheat
2219
CAV Room
Pressurization with
Hot Water Reheat
Table 2. Air Velocity Sensor Connections.
Supply AVS
Application
HI and LO
2215
Supply Pickup
2217
Supply Pickup
2219
Supply Pickup
CAUTION:
The Room Pressurization Controller
– Pneumatic Output controls 24 Vac
loads only. The maximum rating is
12 VA for each DO. For higher VA
requirements, 110 or 220 Vac
requirements, separate
transformers used to power the
load, or DC power requirements,
use an interposing 220V 4-relay
module (TEC Relay Module P/N
540-147).
NOTE: Refer to the unit wiring diagrams or consult
with the local representative if terminations are
missing or are different.
Page 6 of 7
Figure
7
7
7
Exhaust AVS
HI and LO
Exhaust Pickup
Exhaust Pickup
Exhaust Pickup
NOTE:
When wiring any actuator that uses a 0
to 10V control signal and ties AC neutral
to DC common, an additional wire must
connect the actuator AC neutral to the
DC common of the PTEC/TEC AO
being used to control the actuator.
Figure 6. 24 Vac Modulating Control.
Actuator
TEC
Function
Symbol
Connection
1
H
Supply (SP)
2
C
Neutral (SN)
8
AO3 – 15
0 to 10V
(+)
input signal
--
C to AO3
Common
16 (-)
jumper
Terminal
Standard
Connection
Color
G
Red
G0
Black
Y
Gray
--
--
Siemens Industry, Inc.

Advertisement