Mitsubishi EMU4-BM1-MB User Manual page 19

Energy measuring unit energy measuring standard model. energy measuring unit energy measuring high performance model
Table of Contents

Advertisement

6.1.11 External output
Setup the output method of the contact output terminal. Please setup external output in which circuit 1 side circuit or 3 side circuit.
You can't setup in EMU4-BM1-MB.
External output
method
Pulse output
The unit of pulse
output
Alarm output
The object of
alarm output
6.1.12 MODBUS Communication setting
Setup the items for MODBUS communication.Setting values are showed below. This is common regardless of units.
Setting item
MODBUS Address
MODBUS Baud rate
MODBUS Parity
MODBUS Sop bit
6.1.13
Setup for logging
Setup the items for logging using EMU4-LM. Setting values are showed below. This is common regardless of units.
Setting item
Logging ID
Confirmation of logging data
Setting item
Setting range is changed by the value of Full load power.
12
or more
120
or more
1200
or more
12000
or more
120000
or more
1, 2
If the target of external output is 1K, 1L connection side circuit, Set [1].
*
If the target of external output is 3K, 3L connection side circuit, Set [2].
001 to 255
2400, 4800, 9600, 19200, 38400
Non, Even, Odd
1, 2
001~255
OK、Cancel
Setting value
Total load power(kW)
Less than 12
Less than 120
Less than 1200
Less than 12000
Less than 120000
Setting value
Setting value
18
Setting range
0.001, 0.01, 0.1, 1
0.01, 0.1, 1, 10
0.1, 1, 10, 100
1, 10, 100, 1000
10, 100, 1000, 10000
100, 1000, 10000, 100000