York AFFINITY DEZ024 Technical Manual page 53

Heating and air conditioning deq, dex, dey and dez series; r-410a; 2 - 5 ton; 60 hertz
Table of Contents

Advertisement

DEX024-048 Cooling Only With/Without Electric Heat (Continued)
Compressors
Size
(each)
Volt
(Tons)
RLA LRA
208/230-1-60 21.1
96
048
208/230-3-60 13.4
88
(4.0)
460-3-60
6.4
41
1. Minimum Circuit Ampacity.
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or field installed.
DEY060 Cooling Only With/Without Electric Heat
Compressors
Size
(each)
Volt
(Tons)
RLA LRA
208/230-1-60 25.6
118
060
208/230-3-60 17.6
123
(5.0)
460-3-60
9.0
62
1. Minimum Circuit Ampacity.
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or field installed.
Johnson Controls Unitary Products
OD Fan
Supply
Motors
Blower
(each)
Motor
MCC
FLA
FLA
Model
None
2NH04501006 7.5/10
33
1.7
6.8
2NH04501506 11.3/15
2NH04502006
2NH04502506 18.8/25
None
2NH04501025 7.5/10
21
1.7
6.8
2NH04501525 11.3/15
2NH04502025
2NH04502525 18.8/25
None
2NH04501046
10
1.0
6.8
2NH04501546
2NH04502046
2NH04502546
OD Fan
Supply
Motors
Blower
(each)
Motor
MCC
FLA
FLA
Model
None
2NH04501006 7.5/10
40
1.7
9.1
2NH04501506 11.3/15
2NH04502006
2NH04502506 18.8/25
None
2NH04501025 7.5/10
28
1.7
9.1
2NH04501525 11.3/15
2NH04502025
2NH04502525 18.8/25
None
2NH04501046
14
1.0
9.1
2NH04501546
2NH04502046
2NH04502546
Electric Heat Option
kW
Stages
Amps
-
-
-
2
36.1/41.7
2
54.2/62.5
15/20
2
72.2/83.3
2
90.3/104.2 121.3 / 138.7
-
-
-
1
20.8/24.1
1
31.3/36.1
15/20
2
41.7/48.1
2
52.1/60.1
-
-
-
10
1
12
15
1
18
20
2
24.1
25
2
30.1
Electric Heat Option
kW
Stages
Amps
-
-
-
2
36.1/41.7
2
54.2/62.5
15/20
2
72.2/83.3 101.7 / 115.5
2
90.3/104.2 124.2 / 141.6
-
-
-
1
20.8/24.1
1
31.3/36.1
15/20
2
41.7/48.1
2
52.1/60.1
-
-
-
10
1
12
15
1
18
20
2
24.1
25
2
30.1
294604-YTG-G-0511
2
Max Fuse
/
1
3
MCA
Breaker
(Amps)
Size
(Amps)
34.9
45
53.6 / 60.6
60 / 70
76.2 / 86.6
80 / 90
98.8 / 112.7
100 / 125
125 / 150
25.3
35
34.6 / 38.6
35 / 40
47.6 / 53.6
50 / 60
60.6 / 68.6
70 / 70
73.7 / 83.7
80 / 90
15.9
20
23.5
25
31.1
35
38.6
40
46.1
50
2
Max Fuse
/
1
3
MCA
Breaker
(Amps)
Size
(Amps)
42.8
60
56.5 / 63.5
60 / 70
79.1 / 89.5
80 / 90
110 / 125
125 / 150
32.8
40
37.4 / 41.4
45 / 50
50.5 / 56.5
60 / 60
63.5 / 71.5
70 / 80
76.5 / 86.6
80 / 90
21.4
30
26.4
30
33.9
35
41.4
45
49
50
53