Thermostat Display

Status Bar
The status bar at the top of the display consists of
11 icons.
Table 1. Status Bar Icons.
Icon
Name
Occupied
Keypad Lock
Scheduler
Override
Humidity
Control
Indicator
Fan
Fresh Air
Cool Mode
Heat Mode
Heating/Cooling
Stages
Auxiliary
Heating
Navigation Bar
Only one function can be selected at a time. The
small bar (cursor) below the function icon indicates
that a function is selected. Pressing an icon twice
navigates back to the Main screen.
A double bar cursor below the Settings [ ] icon
indicates that you are in Programming mode.
The navigation bar at the bottom of the display
consists of four function icons.
Siemens Industry, Inc.
Meaning
Space is occupied, based
on Schedule.
Keypad is locked.
Unit is running on the local
schedule.
The Scheduler is being
overridden by local control.
Droplet and (+) indicates
humidification relay is on.
Droplet and (-) indicates
dehumidification relay is on.
If neither relay is on, the
water droplet does not
display.
Fan relay is on.
Economizer Enable relay is
on.
The system is actively in
cooling mode.
The system is actively in
heating mode.
Each segment represents
one stage of heating or
cooling.
Auxiliary heating stage:
AUX=Stage 1: Aux 2=Stage
2
Table 2. Navigation Bar Icons.
Icon
Name
Enables adustment of temperature
and humidity (if applicable) setpoints.
Setpoint
Unit will display heating setpoint if in
Heating mode or cooling setpoint if in
Cooling mode.
Enables fan relay to be controlled as
Fan
needed by thermostat (AUTO) or to
Control
be on continuously (ON).
Enables manual changeover between
Heating and Cooling mode. AUTO will
Mode
enable the thermostat to automatically
Selector
switch between heating and cooling
mode as required. OFF will disable all
control functions.
Enables Scheduler, Time/Date, and
Installer Set Up configuration. Also
Settings
enables access to service reminder
and fault messages.
Service Reminders and Fault Messages
·
Service reminders display at the right side of the
screen:
SERVICE UV LAMP
SERVICE HUMIDIFIER
SERVICE AIR FILTER
They are determined by the timer set in the Installer
Setup Menu, and can be cleared by pressing the
Settings [ ] icon, and then SERVICE. See
Clearing Service Reminders.
·
Active fault messages display at the left side of
the home screen:
CONNECTION LOST
DEMAND RESPONSE (Not applicable to this
model)
SERVICE REQUIRED (See Viewing Fault
Messages)
Fault messages are automatically cleared when the
root cause of the failure is resolved.
Connection Lost
If communication with the EcoView Touchscreen is
lost, the thermostat will display CONNECTION LOST
and will control to the locally stored schedule. If a
local schedule has not been configured in the
thermostat, it will control to the last temperature
setpoint sent by the touchscreen.
When the connection is restored, the thermostat will
maintain control to the current setpoint until a new
setpoint is sent from the touchscreen.