York YHKMXH009BARX-FX Service Manual page 240

Table of Contents

Advertisement

Quit condition of oil return:
OR
Oil return procedure in heating mode:
Send oil return signal
Inverter compressor indicated FQY
outdoor motor
4-way valve
PMV auto open angel
all indoor motor ON
Quit condition of oil return
OR
1 minute later after oil return is over
Td‐Tcm>30℃
OR
Ts ‐Tc>30℃
Tc<‐35℃
Max. 10 minutes
60s
0HZ
5s
auto
ON
OFF
450pulse
OFF
Max. 9 minutes(E )
OR
Td‐Tcm<20℃ for 30s(5 minutes later, begin to count )
T s ‐Tc<15℃ for 30 S(5 minutes later, begin to count)
Running for min. 5 minutes ( E )
oil return beginning
oil return frequency
auto(TC control)
300pulse (E )
238
oil return over
120s
Soft startup
0HZ
auto
15s
450 pulse
auto open angle
anti-freeze startup