Low Oil Alarm - Sanyo ECO-i 3-WAY MULTI SYSTEM Service Manual

5 series
Table of Contents

Advertisement

3-WAY ECO-i SYSTEM

15. Low Oil Alarm

Control Functions
Ordinary operation is resumed after system oil recovery control is completed. If a stop occurs again as a result
of a low oil level, this alarm occurs. This alarm will not occur if system oil recovery control has not already been
performed.
However, the alarm may not occur if the outdoor unit where the system oil recovery conditions were met is not
the same as the outdoor unit which stopped due to low oil level. In this case, system oil recovery control may be
performed again.
1

Low oil alarm

Alarm display
H07