WEATHER CONTROLLER
Multi-Mix
FOR CENTRAL HEATING SYSTEMS
OPERATION AND INSTALLATION MANUAL
ISSUE: 1.2_EN
1
04-2018

Advertisement

Table of Contents
loading

Summary of Contents for Salus Multi-Mix

  • Page 1 WEATHER CONTROLLER Multi-Mix FOR CENTRAL HEATING SYSTEMS OPERATION AND INSTALLATION MANUAL ISSUE: 1.2_EN 04-2018...
  • Page 2 ELECTRIC DEVICE UNDER VOLTAGE! Before any action related to the power supply (cables connection, device installation etc.) check if the regulator is not connected to the mains! Installation should be done by a person with appropriate electrical qualifications. Improper cables connection could result in the regulator damage.
  • Page 3: Table Of Contents

    TABLE OF CONTENTS .............. 16 OLAR SAFETY INFORMATION........4 ..........17 EATHER CONTROL GENERAL INFORMATION ........5 ........17 HERMOSTAT SETTINGS INFORMATION ABOUT DOCUMENTATION ..5 HYDRAULIC SCHEMES ........19 DOCUMENTATION STORAGE ......5 ELECTRICAL SYSTEM ......... 27 SYMBOLS USED ........... 5 ..........
  • Page 4: Safety Information

    SAFETY INFORMATION • Electrical system including the controller should be 3-wired and protected with Requirements concerning safety are listed in fuse selected in accordance with used particular sections of this instruction. Apart from loads. them it in necessary to fulfill the following •...
  • Page 5: General Information

    General information - for vital information related with issues The Multi-Mix controller is a universal weather of property damage, health and life risk regulator made in advanced technology that of humans or domestic animals. allows you to manage the operation of the entire...
  • Page 6: Directive Weee 2012/19/Ue

    - schedule, - screed drying function. Directive WEEE 2012/19/UE Purchased product is designed and made of materials of highest quality. The product meets the requirements of the Directive 2012/19/EU of 4 July 2012 on waste electrical and electronic equipment (WEEE), according to which it is marked by the symbol of crossed-out wheeled bin (like below), meaning that product is subjected to separate collection.
  • Page 7: User Settings

    USER SETTINGS Multi-Mix...
  • Page 8: Controller Description

    Controller description varying external temperature, room temperature in heated compartments are kept Controller structure on a set level. Dependent heating circuits The temperature in individual heating circuits can be asked in several ways: - weather control – with consideration to external temperature sensor readings, constant value...
  • Page 9: Main Menu

    5. Navigation bar – indicates location of User menu displayed screen and number of screens possible to be displayed. Screens can be Preset temperatures changed with the use of (8) arrows. H1, H2, H3* ➢ Preset water temperature* 6. Important information –...
  • Page 10: Controller Operation

    Controller operation edition parameter Preset water temperature Activating and deactivating Pump lock thermostat possible only when selecting the Press the switch on the screen in order method adjustment activate controller. “Activate Constant value from the service controller?” message will be displayed. menu.
  • Page 11: Summer - Winter

    of the week. Due to this, entering time periods temperature drops below SUMMER is quick and intuitive. deactivation temperature parameter. Operation within time periods for “DAY” and SUMMER mode, heat “NIGHT”: receivers can be turned off, so make sure that the heat source will „DAY”...
  • Page 12: Work Mode Setting

    Work mode setting defined time periods. Anti – It is possible to select work mode which is freeze function remains active provided that is in active in suitable user’s requirements. operating mode can be selected directly on service menu. It is not possible the main window, press the mode icon.
  • Page 13: Installation And Service Settings

    INSTALLATION AND SERVICE SETTINGS Multi-Mix...
  • Page 14: Controller Assembly

    After installation make sure that the device is Controller assembly properly mounted and it is impossible to detach it from the mounting surface. Environmental conditions regulator casing provides the IP20 Due to fire risk it is forbidden to use the protection rating.
  • Page 15: Temperature Sensors Checking

    External temperature sensors CT-6, CT6-W, CT6-P (Pt1000) Temp. Min. Nom. Max. The controller cooperates only with a CT6-P [°C] [Ω] [Ω] [Ω] type weather sensor. 999,7 1000,0 1000,3 Sensor should be fixed to a coldest wall in the 1096,9 1097,3 1097,7 building.
  • Page 16: Controller Functions

    After an external temperature drop below Control mode ∆ 3°C, the time is expected in the parameter Frost protection - delay e.g. 4 hours. If after this time the external temperature is still 0,5 V under 3°C, a direct heating circuit pump will be activated for 15 minutes, then...
  • Page 17: Weather Control

    to this the boiler will not heat up the DHW building. If the building is less insulated then tank. Similar effect can be obtained by setting the heating curve should be greater. the work mode for DHW tank to Off manually. Loading DHW tank can be also optimized by setting a lowest possible preset temperature of DHW tank.
  • Page 18 control and corrects the water temperature in the heating circuit if the room temperature is still inadequate. A thermostat must be activated for each heating circuit. To do this, set the Thermostat = ON.
  • Page 19: Hydraulic Schemes

    11 Hydraulic schemes Hydraulic scheme no. 1 – basic scheme 1 – boiler without integrated pump 12 – controller 2 – boiler pump 13 – external temperature sensor 3 – direct circuit / hydraulic coupling water temperature 14 – DHW pump sensor 15 –...
  • Page 20 Hydraulic scheme no. 2 - connection of a fireplace with a water jacket Variant A – boiler with integrated pump, variant B – boiler without an integrated pump. 1 – boiler 6 – temperature sensor of water inside the boiler with 2 –...
  • Page 21 Hydraulic scheme no. 3 - diagram “A” with heat buffer 1 – boiler with integrated pump 11 – fireplace regulator 2 – pump 12 – plate heat exchanger 3 – temperature sensor 13 – thermostatic valve protecting return temperature 4 – heat buffer 14 –...
  • Page 22 Hydraulic scheme no. 4 - diagram “B” with heat buffer 1 – boiler 7 – fireplace with water jacket 2 – boiler pump 8 – regulated circuit water temperature sensor (H2) 3 – buffer temperature sensor 9 – circuit pump (H2) 4 –...
  • Page 23 Hydraulic scheme no. 5 - diagram with pelet boiler and with heat buffer 1 – boiler 8 – regulated circuit water temperature sensor 2 – boiler pump 9 – electrical servo of regulated heat circuit 3 – DHW circulation pump 10 –...
  • Page 24 Hydraulic scheme no. 6 - diagram with pelet boiler 1 – boiler 11 – water temperature sensor of adjustable circuit (H3) 2 – solar collector temperature sensor 12 – controller 3 – temperature sensor for direct circuit 13 – weather sensor 4 –...
  • Page 25 Hydraulic scheme no. 7 - diagram “A” with heat buffer with layered charging buffer 1 – controller H2-P,H3-P – adjustable heating circuit pump 3 – fireplace H2-M, H3-M – valve electrical servo of adjustable circuit 4 – heat buffer C-P – DHW circulation pump 5 –...
  • Page 26 Hydraulic scheme no. 8 - diagram “B” with heat buffer with layered charging buffer 1 – boiler 11 - DHW circulating pump 2 – heat buffer 12 - solar panel 3 – additional heat source (fireplace) 13 - solar pump 4 –...
  • Page 27: Electrical System

    12 Electrical system The controller is designed to be supplied with 230V~, 50Hz voltage. System features: • three-wire (with protective wire PE), • made in acc. with currently valid regulations. Caution: Risk of electric shock caused by current from a heat source. Disconnect the controller and heat source electrical supply and make sure there is no dangerous voltage on terminals.
  • Page 28 • cables secured from splitting should be connected to screw terminals of the (6) connector. • cables should be put through cable outlets in the casing (1) and secured from ripping or loosening by a holdfast (5) – break it out from the casing. Zabezpiecza to przewody przed wyrwaniem oraz obluzowaniem.
  • Page 29: Electric Scheme

    Electric scheme...
  • Page 30: Service Menu

    13 Service menu Ustawienia Obieg CWU Entering the menu requires entering Mode a service password. DHW minimum temperature DHW maximum temperature DHW priority Service settings DHW operation extension H1, H2, H3 settings DHW pump circulation mode DHW circuit settings DHW pump circulation standstill time System DHW pump circulation operation time Solar...
  • Page 31 Manual control ➢ H1 circuit pump ➢ H2 circuit pump ➢ Circuit H2 servo ON ➢ Circuit H2 servo OFF ➢ H3 circuit pump ➢ Circuit H3 servo ON ➢ Circuit H3 servo OFF ➢ DHW pump ➢ DHW circulation pump ➢...
  • Page 32: H1 Circuit Settings - Direct, Unregulated

    H1 circuit settings – direct, unregulated Name Range Settings Description ON – enables operation of the circuit, ON (radiators), OFF – disables operation of the circuit, then all parameters Mode (radiators) related to this circuit are invisible and inactive. Constant value – constant preset temperature of water in nonadjustable circuit is maintained.
  • Page 33: H2 And H3 Circuit Settings - Regulated

    H2 and H3 circuit settings – regulated Name Range Settings Description OFF – disables operation of the circuit, then all parameters related to this circuit are invisible and inactive. OFF, ON ON (radiators) – circuit is on and supplies radiators, ON (floor) –...
  • Page 34: Dhw Circuit Settings

    value. Nevertheless in order to avoid frequent servo movements which can shorten its life, adjustment is carried out only when the measured water temperature is lower or higher than the mixer dead zone. Advanced parameter. Do not change it unless it is really 1…6 Proportional range necessary.
  • Page 35: System Settings

    value, loading pump will be enabled and the tank will be loaded again. OFF – disables Legionella function, ON – enables Legionella function. ➢ Every week, at 2:00 a.m., hot tap water will be heated to 70°C in OFF, ON Legionella order to disinfect the DHW tank.
  • Page 36: Solar Settings

    Function saving electricity by stopping the pump of the regulated Time heating circuit when the measured temperature of the circulating 0…60 0min automatic pump water is maintained for 15 minutes above the preset temperature blocking water. Recommended setting: 15 min. OFF –...
  • Page 37: Other Parameters

    Other parameters Name Range Settings Description Activation of external temperature sensor operation for weather control of the heating circuit. In case of sensor damage, the screen ON, OFF Weather sensor displays the message "External temperature sensor damage". Activation of the service will trigger additional parameters in the weather control menu.
  • Page 38: Fuse Replacement

    14 Fuse replacement Note: ………………………………………………………………………… The mains fuse is located under the housing ………………………………………………………………………… cover. It protects the regulator and other ………………………………………………………………………… devices. In case of replacement, use fuse ………………………………………………………………………… 6.3A, 5x20mm. ………………………………………………………………………… In order to take out the fuse, raise the fuse …………………………………………………………………………...
  • Page 40 SALUS-Controls ul. Rolna 4 43-262 Kobielice www.salus-controls.pl...