Weather controller
for control temperature heating circuit (28 pages)
Summary of Contents for Salus Multi-Mix
Page 1
WEATHER CONTROLLER Multi-Mix FOR CENTRAL HEATING SYSTEMS OPERATION AND INSTALLATION MANUAL ISSUE: 1.2_EN 04-2018...
Page 2
ELECTRIC DEVICE UNDER VOLTAGE! Before any action related to the power supply (cables connection, device installation etc.) check if the regulator is not connected to the mains! Installation should be done by a person with appropriate electrical qualifications. Improper cables connection could result in the regulator damage.
TABLE OF CONTENTS .............. 16 OLAR SAFETY INFORMATION........4 ..........17 EATHER CONTROL GENERAL INFORMATION ........5 ........17 HERMOSTAT SETTINGS INFORMATION ABOUT DOCUMENTATION ..5 HYDRAULIC SCHEMES ........19 DOCUMENTATION STORAGE ......5 ELECTRICAL SYSTEM ......... 27 SYMBOLS USED ........... 5 ..........
SAFETY INFORMATION • Electrical system including the controller should be 3-wired and protected with Requirements concerning safety are listed in fuse selected in accordance with used particular sections of this instruction. Apart from loads. them it in necessary to fulfill the following •...
General information - for vital information related with issues The Multi-Mix controller is a universal weather of property damage, health and life risk regulator made in advanced technology that of humans or domestic animals. allows you to manage the operation of the entire...
- schedule, - screed drying function. Directive WEEE 2012/19/UE Purchased product is designed and made of materials of highest quality. The product meets the requirements of the Directive 2012/19/EU of 4 July 2012 on waste electrical and electronic equipment (WEEE), according to which it is marked by the symbol of crossed-out wheeled bin (like below), meaning that product is subjected to separate collection.
Controller description varying external temperature, room temperature in heated compartments are kept Controller structure on a set level. Dependent heating circuits The temperature in individual heating circuits can be asked in several ways: - weather control – with consideration to external temperature sensor readings, constant value...
5. Navigation bar – indicates location of User menu displayed screen and number of screens possible to be displayed. Screens can be Preset temperatures changed with the use of (8) arrows. H1, H2, H3* ➢ Preset water temperature* 6. Important information –...
Controller operation edition parameter Preset water temperature Activating and deactivating Pump lock thermostat possible only when selecting the Press the switch on the screen in order method adjustment activate controller. “Activate Constant value from the service controller?” message will be displayed. menu.
of the week. Due to this, entering time periods temperature drops below SUMMER is quick and intuitive. deactivation temperature parameter. Operation within time periods for “DAY” and SUMMER mode, heat “NIGHT”: receivers can be turned off, so make sure that the heat source will „DAY”...
Work mode setting defined time periods. Anti – It is possible to select work mode which is freeze function remains active provided that is in active in suitable user’s requirements. operating mode can be selected directly on service menu. It is not possible the main window, press the mode icon.
After installation make sure that the device is Controller assembly properly mounted and it is impossible to detach it from the mounting surface. Environmental conditions regulator casing provides the IP20 Due to fire risk it is forbidden to use the protection rating.
External temperature sensors CT-6, CT6-W, CT6-P (Pt1000) Temp. Min. Nom. Max. The controller cooperates only with a CT6-P [°C] [Ω] [Ω] [Ω] type weather sensor. 999,7 1000,0 1000,3 Sensor should be fixed to a coldest wall in the 1096,9 1097,3 1097,7 building.
After an external temperature drop below Control mode ∆ 3°C, the time is expected in the parameter Frost protection - delay e.g. 4 hours. If after this time the external temperature is still 0,5 V under 3°C, a direct heating circuit pump will be activated for 15 minutes, then...
to this the boiler will not heat up the DHW building. If the building is less insulated then tank. Similar effect can be obtained by setting the heating curve should be greater. the work mode for DHW tank to Off manually. Loading DHW tank can be also optimized by setting a lowest possible preset temperature of DHW tank.
Page 18
control and corrects the water temperature in the heating circuit if the room temperature is still inadequate. A thermostat must be activated for each heating circuit. To do this, set the Thermostat = ON.
11 Hydraulic schemes Hydraulic scheme no. 1 – basic scheme 1 – boiler without integrated pump 12 – controller 2 – boiler pump 13 – external temperature sensor 3 – direct circuit / hydraulic coupling water temperature 14 – DHW pump sensor 15 –...
Page 20
Hydraulic scheme no. 2 - connection of a fireplace with a water jacket Variant A – boiler with integrated pump, variant B – boiler without an integrated pump. 1 – boiler 6 – temperature sensor of water inside the boiler with 2 –...
Page 22
Hydraulic scheme no. 4 - diagram “B” with heat buffer 1 – boiler 7 – fireplace with water jacket 2 – boiler pump 8 – regulated circuit water temperature sensor (H2) 3 – buffer temperature sensor 9 – circuit pump (H2) 4 –...
Page 23
Hydraulic scheme no. 5 - diagram with pelet boiler and with heat buffer 1 – boiler 8 – regulated circuit water temperature sensor 2 – boiler pump 9 – electrical servo of regulated heat circuit 3 – DHW circulation pump 10 –...
Page 24
Hydraulic scheme no. 6 - diagram with pelet boiler 1 – boiler 11 – water temperature sensor of adjustable circuit (H3) 2 – solar collector temperature sensor 12 – controller 3 – temperature sensor for direct circuit 13 – weather sensor 4 –...
12 Electrical system The controller is designed to be supplied with 230V~, 50Hz voltage. System features: • three-wire (with protective wire PE), • made in acc. with currently valid regulations. Caution: Risk of electric shock caused by current from a heat source. Disconnect the controller and heat source electrical supply and make sure there is no dangerous voltage on terminals.
Page 28
• cables secured from splitting should be connected to screw terminals of the (6) connector. • cables should be put through cable outlets in the casing (1) and secured from ripping or loosening by a holdfast (5) – break it out from the casing. Zabezpiecza to przewody przed wyrwaniem oraz obluzowaniem.
13 Service menu Ustawienia Obieg CWU Entering the menu requires entering Mode a service password. DHW minimum temperature DHW maximum temperature DHW priority Service settings DHW operation extension H1, H2, H3 settings DHW pump circulation mode DHW circuit settings DHW pump circulation standstill time System DHW pump circulation operation time Solar...
Page 31
Manual control ➢ H1 circuit pump ➢ H2 circuit pump ➢ Circuit H2 servo ON ➢ Circuit H2 servo OFF ➢ H3 circuit pump ➢ Circuit H3 servo ON ➢ Circuit H3 servo OFF ➢ DHW pump ➢ DHW circulation pump ➢...
H1 circuit settings – direct, unregulated Name Range Settings Description ON – enables operation of the circuit, ON (radiators), OFF – disables operation of the circuit, then all parameters Mode (radiators) related to this circuit are invisible and inactive. Constant value – constant preset temperature of water in nonadjustable circuit is maintained.
H2 and H3 circuit settings – regulated Name Range Settings Description OFF – disables operation of the circuit, then all parameters related to this circuit are invisible and inactive. OFF, ON ON (radiators) – circuit is on and supplies radiators, ON (floor) –...
value. Nevertheless in order to avoid frequent servo movements which can shorten its life, adjustment is carried out only when the measured water temperature is lower or higher than the mixer dead zone. Advanced parameter. Do not change it unless it is really 1…6 Proportional range necessary.
value, loading pump will be enabled and the tank will be loaded again. OFF – disables Legionella function, ON – enables Legionella function. ➢ Every week, at 2:00 a.m., hot tap water will be heated to 70°C in OFF, ON Legionella order to disinfect the DHW tank.
Function saving electricity by stopping the pump of the regulated Time heating circuit when the measured temperature of the circulating 0…60 0min automatic pump water is maintained for 15 minutes above the preset temperature blocking water. Recommended setting: 15 min. OFF –...
Other parameters Name Range Settings Description Activation of external temperature sensor operation for weather control of the heating circuit. In case of sensor damage, the screen ON, OFF Weather sensor displays the message "External temperature sensor damage". Activation of the service will trigger additional parameters in the weather control menu.
14 Fuse replacement Note: ………………………………………………………………………… The mains fuse is located under the housing ………………………………………………………………………… cover. It protects the regulator and other ………………………………………………………………………… devices. In case of replacement, use fuse ………………………………………………………………………… 6.3A, 5x20mm. ………………………………………………………………………… In order to take out the fuse, raise the fuse …………………………………………………………………………...
Page 40
SALUS-Controls ul. Rolna 4 43-262 Kobielice www.salus-controls.pl...