ESIE13-03
|
Part 3. Repair
4
4
1
1
3
2
1. Screw
2. Bracket
3. Sound insulation
5.
From the front side, release the 3 velcro strips
1
1
1. Velcro strip
2. Compressor insulation
6.
From the rear side, remove the compressor insulation.
7.
Use a welding blanket (1) to protect the components that surround the refrigerant high pressure sensor (2).
8.
Place 2 wet cooling clamps (3) on the refrigerant high pressure sensor (2) body.
9.
Braze the refrigerant high pressure sensor piping.
13/05/15
|
Version 2.0
Ground source heat pump
Figure 58 - Replacing the refrigerant high pressure sensor - 2
4
1
1
on the compressor insulation
(1)
Figure 59 - Replacing the refrigerant high pressure sensor - 3
1
2
2. Unit specific repair procedures
4
5
3
4. Velcro strip
5. Velcro strip (compressor)
and open the compressor insulation
(2)
3
3. Compressor
3
.
(2)
Page 139