Changed Settings; Reset All Settings - ABB PST30 Installation And Maintenance Manual

Pst series; pstb series
Hide thumbs Also See for PST30:
Table of Contents

Advertisement

Ready?
Yes
Figure 21: All tuning parameters have been passed
Top level
Settings
Figure 22: Basic Settings menu
7
7.10
1SXU 132 021 M0201
Chapter 7
Settings and configuration
Tuning parameters
Six parameters can be tuned individually if a more specific adjustment is required. Each
parameter is described in Chapter 10 " Functions" .
Back
• Start ramp
• Stop ramp
• Initial voltage
• End voltage
• Step down voltage
• Current limit level
When all tuning parameters have been cycled through, the following information will be
displayed, Figure 21. Select Yes if all necessary parameters are tuned. If a new tuning is
required, select Back and follow the step Tune Set above
Application setting
7:2.3 Basic Settings
Basic settings
The Basic settings menu consists of the most common start/stop parameters required for
the set-up. Each parameter can be adjusted separately. For a detailed description of each
Functional settings
parameter, see Chapter 10 " Functions" .
Presentation settings
Enter the Basic settings
Service settings
Enter the menu by selecting Basic Settings.
Setting I
All settings
Set the current that the softstarter will be exposed to (i.e. rated motor current, if the unit is

Changed settings

connected In Line).

Reset all settings

Operation mode
For units connected Inside Delta the Setting I
delta circuit = 58% (1/( 3)) of the rated motor current. Press Store to save the data after
setting the current
External By-Pass contactor (Ext ByPass)
Set the parameter to Yes if an External By-pass Contactor is used, otherwise select No.
Start ramp
Set the ramp time for start.
Stop ramp
Set the ramp time for stop (softstop). Note that this function should only be used for
applications with small flywheel masses, for example pumps and conveyors (minimizes
product damage during the stop).
Initial voltage (Init Volt)
Set the initial voltage level.
End voltage (End Volt)
Set the end voltage level.
Step down
Set the level of the step down voltage. This function is only present if softstop is selected.
Current limit (Current Lim)
Set the current limit level for the start.
Overload Class (OL Class)
Select the desired overload class.
The configuration of the basic setting menu is now completed. It is possible to return to
the top level by pressing Back 3 times.