A.O. Smith ADM-40 Installation, User And Service Manual page 28

Commercial atmospheric water heater
Table of Contents

Advertisement

3
Legend
1 support bracket
2 holes to attach support bracket
3 screws for support bracket
4 holes to attach draught diverter
5 sealing ring
6 screws for draught diverter
7 45° bend
8 chimney pipe
28
Installation
Installing the draught diverter
6
5
4
1. Take the mounting bracket out of the bag.
2. Fit the mounting bracket (1) in such a way that it properly supports the
draught diverter.
3. Drill two holes (2) (3.2 mm bit) for the mounting bracket screws.
4. Screw the mounting bracket tightly to the appliance.
5. Place the draught diverter in the mounting bracket, and mark the centres for
the two holes (4) to be drilled in the top side of the appliance. Remove the
draught diverter from the appliance.
6. Now drill two holes (4) into the top of the appliance (3.2 mm bit).
7. Place the sealing ring (5) on the appliance.
8. Screw the draught diverter tightly in place.
9. Fit:
-
a 45° bend (7) onto the outlet of the draught diverter, followed by:
-
a corrosion-resistant vertical chimney pipe (8) of at least 0.5 metres in
length,
-
the remaining flue components.
Note
Use flue gas discharge materials that comply with the
regulations (1.3 "Regulations").
Note
Make sure that the chimney discharges into an area approved for this type
of appliance.
is
>0,5 m