Installation instructions
What this chapter contains
The chapter contains mechanical and electrical installation instructions.
Planning the installation
See chapter
between the drive output and the filter, maximum motor cable length and other
technical data.
See chapter
can be mounted in an upright position with the output terminals up or down. Other
mounting positions are possible with an extra fan.
Recommended mounting
position
Mounting plate
The filter must be mounted on a grounded metal plate or cabinet frame, or grounded
separately. The structure must be of non-flammable material and strong enough to
carry the weight of the unit.
Encasing
The unprotected (IP00) filter must be encased or placed in a cabinet according to the
local safety requirements.
Electrical connections
Busbars are recommended for connections to the filter input terminals. If cables are
used, they must be rated for at least 105 °C (221 °F). If the filter is not installed in the
same cabinet as the drive, shielded symmetrical cable must be used between the
drive cabinet and the filter enclosure.
Technical data
for allowed ambient conditions, maximum cable length
Dimensional drawings
Output terminals
Input terminals
for the dimensions and fastening holes. The filter
Alternative mounting
position
Installation instructions
13