Errors, Disturbances, Warnings - SMA SUNNY BOY 1600TL Installation Manual

Pv inverter
Hide thumbs Also See for SUNNY BOY 1600TL:
Table of Contents

Advertisement

SMA Solar Technology AG
MPP Peak
The inverter is operating in MPP mode above its nominal power.
MPP-Search
The inverter is calculating the MPP.
Grid
Grid monitoring. If irradiation is low or an error has occurred, this message
monitoring
appears before the inverter is connected to the electricity grid.
Offset
Offset alignment of the measurement electronics
Riso
Measuring the insulation resistance of the PV plant
Disturbance
The inverter has detected a disturbance. The specific disturbance message is also
displayed (see Section 10.2.3 "Errors, Disturbances, Warnings", page 47).
Stop
Operation interrupted
V-Const
Constant voltage mode.
Waiting
The conditions for grid connection are not (yet) fulfilled.

10.2.3 Errors, Disturbances, Warnings

Errors, disturbances and warnings are shown in the display and start in the first line with the word
"Error", "Fault" or "Warning". In the second line of the display, the cause of the error, fault or warning
is shown.
Message
!PV-Overvoltage!
!DISCONNECT DC!
Installation Manual
Description and Corrective Measures
Overvoltage at the DC input. The inverter may be destroyed. This message
is additionally highlighted by rapid flashing of the backlight.
Corrective measures:
1. Disconnect the miniature circuit-breaker.
2. If there is an external DC switch-disconnector, turn it off.
3. If an ESS is in use, disconnect it.
4. Release and disconnect all DC connectors using a screwdriver
(blade width 3.5 mm).
– Insert a screwdriver into one of the side slots.
– Pull the DC connectors out.
5. Check whether the DC voltage is below the maximum input voltage of
the inverter. If the DC voltage is below the maximum input voltage of
the inverter, reconnect the DC connectors to the inverter.
If the DC voltage is above the maximum input voltage of the inverter,
check the PV plant design or contact the installer of the PV array.
6. If this message recurs frequently, disconnect the inverter from voltage
sources (see Section 8) and contact the SMA Service Line.
10  Troubleshooting
SB13_21TL-IA-en-65
47