System Configuration; Figure 4: System Configuration - Roberts Gorden System Control HP 120 V 1 Installation & Operation Manual

Roberts gordon heating equipment installation, operation and service manual
Table of Contents

Advertisement

S
C
I
, O
YSTEM
ONTROL
NSTALLATION
PERATION AND
For the EP-203 (3 Ø), EP-303 (3 Ø), EP-100, EP-201
and EP-301 208/230 V (1 Ø) pumps, use the 17 Amp
contactor package (P/N 10050011).
For the EP-301 pumps that are operated with 120 V
(1 Ø) use the 28 Amp contactor package (P/N
10050012). The contents are listed below:
Contactor Packages
Part No.
Description
10050011 Contactor Package 17A
10001002
Enclosure IEC metal 8X6X6 NEMA 1
90600200
CONT 208-600 17A (A16-30-10-84)
10050012 Contactor Package 28A
10001002
Enclosure IEC metal 8X6X6 NEMA 1
90600205
CONT 208-600 28A (A26-30-10-84)
All pump motors are equipped with thermal
overloads.
3.3.3 If an outside air blower is to be used with any of
the above options, See Page 10, Figure 8.

FIGURE 4: System Configuration

AC POWER IN
PUMP 1
ZONE 1
G
N
L
N
L
N
L
6
S
M
ERVICE
ANUAL
ZONE 2
ZONE 3
ZONE 4
PUMP 2
N
L
N
L
N
L
N
L

3.4 System Configuration

See Page 6, Figure 4 for details. Below the ribbon
cable J2 connector, there are six configurable jump-
ers. They indicate whether the thermostat for each
zone uses an anticipator. If the thermostat for that
associated zone has an anticipator, then use a
jumper to cover both pins for that zone. If the thermo-
stat for the associated zone does not use an antici-
pator, then cover the right side pin only.
The bottom two jumpers are associated with Pump 2
operation. They indicate whether Pump 2 is active
and which zones are associated with it. Pump 2 can
only be associated with Zone 3 and/or Zone 4. To
enable Pump 2, use a jumper to cover both pins for
the zone(s) that will operate on Pump 2. To disable
Pump 2, cover only the right side of the pin of zone 3
and 4.
ANTICIPATOR
LOAD ENABLE
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE 3
ZONE 4
PUMP 2
OPERATION
ENABLE
ANTICIPATOR
LOAD ENABLE
ZONE 1
ZONE 2
ZONE 3
ZONE 4
ZONE 3
ZONE 4
PUMP 2
OPERATION
ENABLE
FEATURE
ENABLED
FEATURE
DISABLED