NGC-UIT2-ORD
User Interface termInal for raychem nGc systems InstallatIon InstrUctIons
ApprovAls / certificAtions
Nonhazardous Locations
CONFORMS TO UL STD 60950-1
CERTIFIED TO CSA STD C22.2
NO. 60950-1
3128486
General
Area of Use
Nonhazardous, indoors or outdoors
(IP65, Type 4)
Supply Voltage
9 – 30 Vdc, 3.6 – 1.2 A
Operating
–30°C to 50°C (–22°F to 122°F)
Temperature
Min. Storage
–30°C to 80°C (–22°F to 176°F)
Temperature
Dimensions
279 mm W X 229 mm H X 70 mm D
(11 in. W X 9 in. H X 2.75 in. D)
Alarm outputs
Transistor open
Three open collector outputs, with a range of 5 – 30
collector outputs
Vdc with a max. sink current of 500 mA
Use to drive
Relays may be assigned for alarm outputs.
external relays
lcD Display
Display
LCD is a 8.4 in. XGA, color TFT transflective device
with integral LED backlight
Touch Screen
5-wire resistive touch screen interface for user entry
WARNING:
FIRE HazaRd: The NGC-UIT2-ORD must not be used in hazardous
locations. Electrical components within the unit could ignite
flammable gases. Do not install the unit where it may be exposed
to flammable gases.
inDustriAl HeAt trAcinG solutions
NGC-UIT2-ORD
installed in a panel
IMPORTANT:
The NGC-UIT2-ORD is an electronic unit. During installation, take the
following precautions to avoid damage to its electronic components.
• Handle with care to avoid mechanical damage.
• Keep electronics dry.
• Avoid exposure to static electricity.
GB-RaychemNGCUIT20RD-IM-H58531 INSTALL-168 05/15
Description
The NGC-UIT2-ORD is a panel mounted display used in conjunction
with other Raychem control and monitoring devices. The NGC-UIT2-
ORD is rated IP 65 (Type 4), and can be mounted indoors or outdoors.
The NGC-UIT2-ORD kit includes all hardware required for mounting
in a suitable electrical panel. Additional materials are required for
electrical connections and are detailed below. These instructions
describe how to mount the NGC-UIT2-ORD in an electrical panel and
are intended only for personnel experienced in panel construction.
tools requireD
• Masking tape
• Metal file
• In-line torque wrench with 8 mm (5/16 in) socket
• Jig saw (recommend using carbon steel blade with 24TPI)
ADDitionAl MAteriAls (to be orDereD sepArAtely)
qty Description
2 9 pin D-SUB to 10 pin terminal
block PCB
2 Serial communication cable
3 Alarm relays – 12 Vdc, 12 A,
SPDT
3 Alarm relay sockets
1 Push to test alarm light 120 or 230 Vac
note: Equivalent parts may be used.
network connection
Local/
RS-232/RS-485 ports may be used to communicate
Remote Port
with host computers (Raychem Supervisor Software)
or DCS
Local RS-232
A non-isolated, 9 pin D sub male
Remote RS-485 #2 2-wire isolated, 9 pin D sub male
Data Rate
9600 to 57600 baud.
Maximum cable
For RS-485 not to exceed 1200 m (4000 ft). Cable to
length
be shielded twisted pair.
Field Port
RS-485, 2-wire isolated. Used to communicate with
external devices, such as NGC-30-CRM and RMM2.
Maximum cable length not to exceed 1200 m (4000
ft). Cable to be shielded twisted pair.
Field RS-485 #1
2-wire isolated, 9 pin D sub male
Data Rate
To 9600 baud
LAN
10/100 Base-T Ethernet port with Link and Activity
Status LEDs
USB Ports
USB 2.0 Host port Type A receptacle (X2)
• Avoid contamination with metal filings, liquids, or other foreign
matter.
• Take care to protect the user interface board on the enclosure door.
• Use agency-approved conduit bushings, adapters, and cable
glands to keep the enclosure protected from dust and fluids.
• #16 (3/16) drill bit
Manufacturer
Manufacturer
part number
Phoenix Contacts 2315162
L-COM
CSMN9MF-xx
xx = Length in ft
Tyco Electronics RTB14012F
Tyco Electronics RT78724
1 / 8