Rheem PH-16(FISN)(FISP) Use And Care Manual page 13

Indoor and outdoor gas tankless water heater
Table of Contents

Advertisement

Installing the water heater:
Outdoor Water Heater
Caulk
If soffit vent is too close,
block off and install new
vent at another location
Inside
corner
6' (1.8 m) caulk
zone
Caulk
4'
12" (30 cm)
(1.2 m)
Indoor Water Heater
Caulk
If soffit vent is too close,
block off and install new
vent at another location.
Inside
Caulk
Corner
6' (1.8 m)
Caulk Zone
4'
(1.2 m)
WARNING
:
Moisture in the flue gas will condense as
it leaves the vent terminal. In cold weather this condensate
can freeze on the exterior wall, under the eaves and on
surrounding objects. Some discoloration on the exterior of
the building is to be expected. However, improper location
or installation can result in severe damage to the structure
or exterior finish of the building.
Rising moisture will collect under eaves
(1.8 m)
6'
6' (1.8 m)
caulk zone or
to edge of
window etc., starting
within 6' (1.8 m)
Caulk
Rising moisture will
collect under eaves.
6'
(1.8 m)
6' (1.8 m)
Caulk
zone or to edge of window
etc.,starting within 6' (1.8 m).
Caulk
RTV silicone caulk
Wall thimble face plate
12"(30 cm)
Additional Considerations
Do NOT install vent terminal under any patio or deck.
To help prevent moisture from freezing on walls and under
eaves, do not locate vent terminal on the side of a building with
prevailing winter winds.
To help prevent water lines from freezing, do not locate vent
terminal on the side of a building with prevailing winter winds.
Do NOT locate vent terminal too close to shrubbery, as flue gases
may damage them.
Caulk all cracks, seams and joints within six (6) feet (1.8 m) of vent
terminal.
Caulk around thimble face plate for weather tight seal.
All painted surfaces should be primed to lessen the chance of
physical damage. Painted surfaces will require maintenance.
Insulate vent pipe of water heaters exposed to cold conditions
(attics, crawl spaces, etc.) with inflammable material to help prevent
moisture from accumulating in vent pipe. The insulation should be
rated for the temperature and should not contain substances that
corrode the vent pipe.
Do NOT extend exposed vent pipe of indoor water heaters outside of
building.
Guard vent against accidental contact with people and pets.
Install outdoor water heater such that air inlet and flue outlet is
above anticipated snow level.
13