SECTION 6: ELECTRIC STARTERS AND BATTERIES
b. Once stabilized, draw in the final sample.
c. Draw in only enough electrolyte to obtain a reading —
do not let the hydrometer float hit the suction bulb.
d. Hold the hydrometer vertically and shake it gently to
make sure the float is not sticking to the inside of the
glass barrel.
e. Read and record the specific gravity reading.
4. Check the temperature of the fluid. Add the required
points if temperature is above 80 F. Subtract the required
points if below 80 F (see Figure 6.3).
5. Check and record readings of the remaining cells in the
6. When all cells have been checked, subtract the lowest
In Figure 6.3, the highest reading is 1.260, and the lowest
reading is 1.225. Subtract 1.225 from 1.260 to obtain a 35
point difference.
Figure 6.3 — Using a Battery Hydrometer
28
same manner.
reading obtained from the highest reading. If there is more
than 30 points difference, the battery is probably defec-
tive and should be replaced.